How to Install Your Pulse Counter Module
Publication 1794-6.5.16 – September 1998
Methods of wiring the terminal base units are shown in the
illustration below.
Wiring the Terminal Base Units (1794-TB3G shown)
Wiring when total current draw is less than 10A
Wiring when total current draw is greater than 10A
Daisy-chaining
Individual
Total current draw through any base unit must not be greater than 10A
Combination
24V dc
24V dc
24V dc
24V dc
24V dc
24V dc
Note: Use this configuration if using any
“noisy” dc digital I/O modules in your system.
Pulse Counter Module wiring separate from digital wiring.
Note: All modules powered by the same power supply
must be pulse, frequency or TC/RTD/mV modules for this configuration.
Note: All modules must be pulse, frequency or TC/RTD/mV modules for this configuration.
Pulse Counter
Module
Digital Input
Module
ATTENTION: Do not daisy chain power or
ground from the terminal base unit to any ac or dc
digital module terminal base unit.
!
Digital Output
Module
Digital Input
Module
Pulse Counter
Module
TC/RTD/mV
Module
Pulse Counter
Module
TC/RTD/mV
Module
Pulse Counter
Module
Pulse Counter
Module
Pulse Counter
Module
Pulse Counter
Module