Rockwell Automation Publication 5094-IN010A-EN-P - May 2018

FLEX 5000 Terminal Base Assembly Modules

Prevent Electrostatic Discharge

Electrical Safety Considerations

 

WARNING: 

Special Conditions for Safe Use:

• This equipment is not resistant to sunlight or other sources of UV radiation.
• This equipment shall be mounted in an ATEX/IECEx Zone 2 certified enclosure with a minimum ingress protection rating of at least IP54 (in accordance with 

EN/IEC 60079-15) and used in an environment of not more than Pollution Degree 2 (as defined in EN/IEC 60664-1) when applied in Zone 2 environments. The 
enclosure must be accessible only by the use of a tool.

• This equipment shall be used within its specified ratings defined by Rockwell Automation.
• Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 140% of the peak rated voltage when 

applied in Zone 2 environments.

• The instructions in the user manual shall be observed.
• This equipment must be used only with ATEX/IECEx certified Rockwell Automation backplanes.
• Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this 

product.

• Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
• Earthing is accomplished through mounting of modules on rail.
• Devices shall be used in an environment of not more than Pollution Degree 2.

ATTENTION: 

This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when 

you handle this equipment:

• Touch a grounded object to discharge potential static.
• Wear an approved grounding wriststrap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• Use a static-safe workstation, if available.
• Store the equipment in appropriate static-safe packaging when not in use.

ATTENTION: 

• Do not wire more than 1 conductor on any terminal.
• In case of malfunction or damage, no attempts at repair should be made. The module should be returned to the manufacturer for repair. Do not dismantle 

the module.

• This equipment is certified for use only within the surrounding air temperature range of -40…+70 °C (-40…+158 °F) The equipment must not be used 

outside of this range.

• Use only a soft dry anti-static cloth to wipe down equipment. Do not use any cleaning agents.

IMPORTANT

Any illustrations, charts, sample programs, and layout examples shown in this publication are intended solely for the purposes of example. Since there are 
many variables and requirements associated with any particular installation, Rockwell Automation does not assume responsibility or liability for actual use 
based upon the examples shown in this publication.

ATTENTION: 

Read this document and the documents listed in the 

Additional Resources on page 15

 section about installation, configuration, and operation of 

this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring 
instructions in addition to requirements of all applicable codes, laws, and standards. 

ATTENTION: 

Installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained 

personnel in accordance with applicable code of practice.

Summary of Contents for FLEX 5000

Page 1: ...ovable terminal blocks needed as a terminal base for your specific FLEX 5000 I O modules Terminal base assemblies are a required part of the FLEX 5000 I O system FLEX 5000 I O systems are used with so...

Page 2: ...cati nella sezione Altre risorse riguardanti l installazione la configurazione ed il funzionamento dell apparecchiatura Gli utenti devono leggere e comprendere le istruzioni di installazione e cablagg...

Page 3: ...s dangereux Lorsque plusieurs produits sont combin s dans un syst me le code de temp rature le plus d favorable code de temp rature le plus faible peut tre utilis pour d terminer le code de temp ratur...

Page 4: ...andle this equipment Touch a grounded object to discharge potential static Wear an approved grounding wriststrap Do not touch connectors or pins on component boards Do not touch circuit components ins...

Page 5: ...XT 5094 RTB3S 5094 RTB3SXT RTB MB FRONT VIEW Backplane connector DIN rail mount System connector Threaded insert for RTB captive fastener DIN rail actuator RTB locking pegs FRONT VIEW Keyswitches set...

Page 6: ...0 I O modules MB type depends on your system requirements Refer to FLEX 5000 I O Modules Specifications Technical Data publication 5094 TD001 for system requirements Removable terminal block RTB type...

Page 7: ...tion see the publications that are listed in Additional Resources on page 15 Tools The following tools are needed screw driver such as the 1492 N90 terminal block screw driver with hardened 3mm diamet...

Page 8: ...shield bar to the bottom row of terminals on the 5094 RTB3 or the 5094 RTB3T 1 Insert the mounting hooks of the shield bar into the holes under the last row of terminals on the RTB 2 Pivot the shield...

Page 9: ...urely mounted You can use an Allen Bradley 199 DR1 46277 3 EN50022 35 x 7 5 mm 1 38 x 0 30 in DIN rail with a FLEX 5000 I O system RemoveorReplaceOptionalSAPowerJumpersfromTerminalBases 1 Unscrew term...

Page 10: ...e 8 RemoveorReplacetheTerminalBase 1 If there is an I O module installed remove the I O module from the terminal base 2 Turn the DIN rail actuator to the unlocked position 3 Carefully pull the termina...

Page 11: ...dividual I O module installation instructions 5 Connect V DC power to terminal SA 6 Connect V DC common to terminal SA WARNING If you connect or disconnect wiring while the field side power is on an e...

Page 12: ...terminal base WARNING If you connect or disconnect wiring while power is applied an electrical arc can occur This could cause an explosion in hazardous location installations Be sure that power is rem...

Page 13: ...nalog Output Module Specialty Module Counter Module Modules with total SA loading 10 A Modules with total SA loading 10 A Modules with total SA loading 10 A Modules with total SA loading 80 of SA 5094...

Page 14: ...allation instructions for your specific I O module Insulation stripping length Screw 0 34 2 5 mm2 22 14 AWG 12 mm 1 mm 0 47 in 0 04 in Spring 0 34 1 3 mm2 22 16 AWG 10 mm 1 mm 0 39 in 0 04 in 2 5 mm2...

Page 15: ...cing Output Modules Installation Instructions publication 5094 IN004 Provides information on how to install FLEX 5000 digital output I O modules FLEX 5000 Digital 8 point Isolated Relay Output Module...

Page 16: ...needs better If you have any suggestions on how to improve this document complete the How Are We Doing form at http literature rockwellautomation com idc groups literature documents du ra du002_ en e...

Reviews: