FLEX 5000 Terminal Base Assembly Modules
Remove or Replace Shield Bar from Terminal Base
1. Insert a small screwdriver into the shield bar release latch, and lift to dislodge the locking pegs.
2. Pivot the shield bar forward and unhook it from the RTB.
3. To replace a shield bar, refer to
Install the Shield Bar on page 8
.
Remove or Replace RTB from Mounting Base
1. If there is an I/O module installed, remove the I/O module from the terminal base.
2. Switch off field power.
3. Use a screwdriver to turn the RTB connection mating screw counter clockwise.
4. Pull the RTB away from the mounting base.
5. To replace an RTB, refer to
Assemble the Removable Terminal Block and the Mounting Base on page 8
Remove or Replace the Terminal Base
1. If there is an I/O module installed, remove the I/O module from the terminal base.
2. Turn the DIN rail actuator to the unlocked position.
3. Carefully pull the terminal base away from the DIN rail along the interlocking system connectors of the adjacent terminal base assembly.
Install the End Cap
An end cap ships with the adapter.
You must install an end cap on the right side of the last terminal base in a FLEX 5000 I/O system. The end cap covers the exposed interconnections
on the adapter module or on the last terminal base in the system. If you do not install the end cap before powering the system, equipment damage or
injury from electric shock can result.
Once you have installed all your modules for your system, install the end cap on the last terminal base.
1. Make sure that the end cap is unlocked.
If the end cap is locked, pull the tab until it clicks.
Tab
Unlocked
Locked
Locked
Unlocked
Tab