Rockwell Automation Publication 5094-IN010A-EN-P - May 2018

11

FLEX 5000 Terminal Base Assembly Modules

2. Align the end cap with interlocking system connector on the last terminal base in the system.

3. Push the end cap towards the DIN rail

4. Press the Locking tab until it clicks.

Wire the Terminal Base

The RTB of the terminal base assembly is wired according to the installed I/O module requirements. For more wiring details, refer to each 
individual I/O module.

1. Confirm that all sources of power to the module and terminal base are turned off.

2. Strip insulation from the wires that you connect to the terminal base.

3. Connect the wires to the terminal base.

4. Connect I/O module wiring to terminals 0…15, 16…31, and 32…47 as indicated in individual I/O module installation instructions.

5. CV DC power to terminal SA+/+.

6. Connect V DC common to terminal SA-/-.

WARNING: 

If you connect or disconnect wiring while the field-side power is on, an electrical arc can occur. This could cause an explosion in hazardous location 

installations. Be sure that power is removed or the area is nonhazardous before proceeding.

TB Type

Action

Screw

0.34...2.5 mm

2

 (22…14 AWG) =Strip 12 mm ± 1 mm (0.47 in ± 0.04 in) of insulation from the wires

Spring

0.34...1.3 mm

2

 (22...16 AWG) = Strip 10 mm ± 1 mm (0.39 in ± 0.04 in) of insulation from the wires

2.5 mm

2

 (14 AWG) = Strip 15 mm ± 1 mm (0.59 in ± 0.04 in) of insulation from the wires

TB Type

Action

Screw

1. Insert the wire into the terminal.
2. Turn the screwdriver to close the terminal on the wire. Torque the screw to 0.4 N•m (3.5 lb•in).

Spring

Push the wire into the terminal.
If the wire is too thin, crimp a wire ferrule on the wire and insert it.

Spring-type TB

Screw-type TB

Summary of Contents for FLEX 5000

Page 1: ...ovable terminal blocks needed as a terminal base for your specific FLEX 5000 I O modules Terminal base assemblies are a required part of the FLEX 5000 I O system FLEX 5000 I O systems are used with so...

Page 2: ...cati nella sezione Altre risorse riguardanti l installazione la configurazione ed il funzionamento dell apparecchiatura Gli utenti devono leggere e comprendere le istruzioni di installazione e cablagg...

Page 3: ...s dangereux Lorsque plusieurs produits sont combin s dans un syst me le code de temp rature le plus d favorable code de temp rature le plus faible peut tre utilis pour d terminer le code de temp ratur...

Page 4: ...andle this equipment Touch a grounded object to discharge potential static Wear an approved grounding wriststrap Do not touch connectors or pins on component boards Do not touch circuit components ins...

Page 5: ...XT 5094 RTB3S 5094 RTB3SXT RTB MB FRONT VIEW Backplane connector DIN rail mount System connector Threaded insert for RTB captive fastener DIN rail actuator RTB locking pegs FRONT VIEW Keyswitches set...

Page 6: ...0 I O modules MB type depends on your system requirements Refer to FLEX 5000 I O Modules Specifications Technical Data publication 5094 TD001 for system requirements Removable terminal block RTB type...

Page 7: ...tion see the publications that are listed in Additional Resources on page 15 Tools The following tools are needed screw driver such as the 1492 N90 terminal block screw driver with hardened 3mm diamet...

Page 8: ...shield bar to the bottom row of terminals on the 5094 RTB3 or the 5094 RTB3T 1 Insert the mounting hooks of the shield bar into the holes under the last row of terminals on the RTB 2 Pivot the shield...

Page 9: ...urely mounted You can use an Allen Bradley 199 DR1 46277 3 EN50022 35 x 7 5 mm 1 38 x 0 30 in DIN rail with a FLEX 5000 I O system RemoveorReplaceOptionalSAPowerJumpersfromTerminalBases 1 Unscrew term...

Page 10: ...e 8 RemoveorReplacetheTerminalBase 1 If there is an I O module installed remove the I O module from the terminal base 2 Turn the DIN rail actuator to the unlocked position 3 Carefully pull the termina...

Page 11: ...dividual I O module installation instructions 5 Connect V DC power to terminal SA 6 Connect V DC common to terminal SA WARNING If you connect or disconnect wiring while the field side power is on an e...

Page 12: ...terminal base WARNING If you connect or disconnect wiring while power is applied an electrical arc can occur This could cause an explosion in hazardous location installations Be sure that power is rem...

Page 13: ...nalog Output Module Specialty Module Counter Module Modules with total SA loading 10 A Modules with total SA loading 10 A Modules with total SA loading 10 A Modules with total SA loading 80 of SA 5094...

Page 14: ...allation instructions for your specific I O module Insulation stripping length Screw 0 34 2 5 mm2 22 14 AWG 12 mm 1 mm 0 47 in 0 04 in Spring 0 34 1 3 mm2 22 16 AWG 10 mm 1 mm 0 39 in 0 04 in 2 5 mm2...

Page 15: ...cing Output Modules Installation Instructions publication 5094 IN004 Provides information on how to install FLEX 5000 digital output I O modules FLEX 5000 Digital 8 point Isolated Relay Output Module...

Page 16: ...needs better If you have any suggestions on how to improve this document complete the How Are We Doing form at http literature rockwellautomation com idc groups literature documents du ra du002_ en e...

Reviews: