1
Publication 1784-6.5.30 - February 2001
Appendix
D
Changing the Network Baud Rate
Required Procedure
This Appendix summarizes what you have to do to change the baud
rate of an existing DeviceNet network. You must perform the steps
below in the following order:
1.
Close all applications that might be using the 1784-PCIDS driver.
This includes any Soft Control engines as well as explicit
messaging applications.
2.
Delete the 1784-PCIDS driver from RSLinx.
3.
Change the baud rate on any non-autobaud devices on your
network by setting the dip switches or individually programming
the devices accordingly.
4.
Power down your programming terminal/personal computer and
your 24V network supply.
5.
Turn on your 24V network power.
6.
Turn on your personal computer
.
7.
Re-install the 1784-PCIDS driver in RSLinx, using the new baud
rate.
Summary of Contents for DeviceNet 1784-PCIDS
Page 1: ...DeviceNet PCI Communication Interface Card 1784 PCIDS CPCIDS User Manual Allen Bradley Parts...
Page 4: ......
Page 12: ...Publication 1784 6 5 30 February 2001 P 8 About This User Manual...
Page 38: ...Publication 1784 6 5 30 February 2001 3 8 Setting Up the Hardware for the Example Network...
Page 58: ...Publication 1784 6 5 30 February 2001 4 20 Configuring the DeviceNet Network...
Page 68: ...Publication 1784 6 5 30 February 2001 5 10 Using IOLinx To Test the Example Network...
Page 82: ...Publication 1784 6 5 30 February 2001 B 12 Creating and Running a SoftLogix 5 Application...
Page 94: ...Publication 1784 6 5 30 February 2001 D 2 Changing the Network Baud Rate...
Page 99: ...Allen Bradley Parts...
Page 101: ...DeviceNet PCI Communication Interface Card User Manual Allen Bradley Parts...