1786-5.7 - February 1999
2
ControlNet Coax Tap
CSA Statement
When the product is marked with the CSA Hazardous Location marking, it
is suitable for use in Class I, Division 2 Hazardous Locations and
nonhazardous locations only when installed with products bearing the
Allen-Bradley ControlNet name or logo, and like certifications.
CSA logo is a registered trademark of the Canadian Standards Association.
CSA Hazardous Location Approval
CSA certifies products for general use as well as for use in hazardous locations.
Actual CSA certification is indicated by the
product label
as shown below, and not by statements in any user documentation.
Example of the CSA certification product label:
To comply with CSA certification for use in hazardous locations, the following information becomes a part of the product literature for
this CSA-certified industrial control product.
•
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D, or non-hazardous locations only.
•
The products having the appropriate CSA markings (that is, Class I, Division 2, Groups A, B, C, D) are certified for use in other
equipment where the suitability of combination (that is, application or use) is determined by the CSA or the local inspection office
having jurisdiction.
Important:
Due to the modular nature of a programmable control system, the product with the highest temperature rating determines
the overall temperature code rating of a programmable control system in a Class I, Division 2, location. The temperature code rating is
marked on the product label as shown.
Temperature code rating:
The following warnings apply to products having CSA certification for use in hazardous locations.
ATTENTION:
Explosion hazard -
•
Substitution of components may impair suitability for Class I, Division 2.
•
Do not replace components unless power has been switched off or the area is known to be non-hazardous.
•
Do not disconnect equipment unless power has been switched off or the area is known to be non-hazardous.
•
Do not disconnect connectors unless power has been switched off or the area is known to be non-hazardous.
Secure any user-supplied connectors that mate to external circuits on this equipment by using screws, sliding
latches, threaded connectors, or other means such that any connection can withstand a 15 Newton (3.4 lb.)
separating force applied for a minimum of one minute.
CL I, DIV 2
GP A,B,C,D
TEMP
CL I, DIV 2
GP A,B,C,D
TEMP