Technical Specifications
Additional Resources
These documents contain additional information concerning related products from Rockwell Automation.
You can view or download publications at
http://www.rockwellautomation.com/literature/
. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.
Attribute
1786-RPA/B
1786-RPCD
1786-RPFM
1786-RPFS
1786-RPFRL/B, 1786-RPFRXL/B
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold)
IEC 60068-2-2 (Test Bd, Operating Dry Heat)
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Voltage and current ratings, max
Input: 700 mA @ 24V DC, SELV
Output: 1.6 A @ 5V DC
Backplane: 400 mA @ 5V DC
Backplane: 400 mA @ 5V DC
Backplane: 300 mA @ 5V DC
Input: 570 mA @ 5V DC
Relay: 900 mA @ 30V DC, Class 2,
resistive only
Power consumption, max
16.8 W
2 W
2 W
1.5 W
2.8 W
Power dissipation, max
8.8 W
2 W
2 W
1.5 W
2.8 W
Isolation voltage
N/A (SELV), functional insulation
type, ContolNet to system
N/A (SELV), functional insulation
type, ContolNet to system and
between ControlNet channels
—
—
50V (continuous), basic insulation
type, relay contacts to system
Wire size
0.21…3.3 mm
2
(24…12 AWG)
solid or stranded copper wire rated
at 105 °C (221 °F) or greater, 1.2
mm (3/64 in.) insulation max for
power connections
NA
—
—
0.25…2.5 mm
2
(22…14 AWG)
solid or stranded copper wire rated
at 75 °C (167 °F) or greater, 1.2 mm
(3/64 in.) insulation max for power
connections
Wiring category
2 - on power ports
2 - on ControlNet ports
2 - on ControlNet ports
—
—
2 - on relay ports
Enclosure type rating
None (open-style)
North American temp code
T5
T5
T5
T5
T4A
ATEX temp code
T5
T5
T5
T5
—
IECE x temp code
T5
T5
T5
T5
—
Resource
Description
ControlNet Modular Repeater Adapter Installation Instructions, publication
Installation instructions for 1786-RPA modular repeater adapters.
ControlNet Modular Repeater Short-distance Fiber Module Installation Instructions, publication
Installation instructions for 1786-RPFS repeater modules, short-distance fiber.
ControlNet Modular Repeater Medium-distance Fiber Module Installation Instructions, publication
Installation instructions for 1786-RPFM repeater modules, medium-distance fiber.
ControlNet Fiber Ring Modules Installation Instructions, publication
Installation instructions for 1786-RPFRL and 1786-RPFRXL repeater modules, fiber ring
ControlNet Modular Repeater Dual Copper Module Installation Instructions, publication
Installation instructions for 1786-RPCD repeater modules,dual copper.
ControlNet Fiber Media Planning and Installation Guide, publication
Information about installing a ControlNet fiber media system.
ControlNet Coax Media Planning and Installation Guide, publication
Information about installing a ControlNet coaxial media system.
Industrial Automation Wiring and Grounding Guidelines, publication
General guidelines for installing a Rockwell Automation® industrial system.
Product Certifications website,
http://www.rockwellautomation.com/products/certification
Declarations of conformity, certificates, and other certification details.