Allen-Bradley ControlNet 1786-RPCD Product Information Download Page 6

Publication 1786-PC001B-EN-P - January 2015

PN-254949 

Supersedes 1786-PC001A-EN-P - September 2014

Copyright © 2015 Rockwell Automation, Inc. All rights reserved.  Printed in the U.S.A.

Allen-Bradley and Rockwell Automation are trademarks of Rockwell Automation, Inc.

Trademarks not belonging to Rockwell Automation are property of their respective companies.

Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400

Rockwell Automation maintains current product environmental information on its website at 

http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page

.

Technical Specifications

Additional Resources

These documents contain additional information concerning related products from Rockwell Automation.

You can view or download publications at 

http://www.rockwellautomation.com/literature/

. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.

Attribute

1786-RPA/B

1786-RPCD

1786-RPFM

1786-RPFS

1786-RPFRL/B, 1786-RPFRXL/B

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold)

IEC 60068-2-2 (Test Bd, Operating Dry Heat)

IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F) 

Temperature, surrounding air, max

60 °C (140 °F)

Voltage and current ratings, max

Input: 700 mA @ 24V DC, SELV

Output: 1.6 A @ 5V DC

Backplane: 400 mA @ 5V DC

Backplane: 400 mA @ 5V DC

Backplane: 300 mA @ 5V DC

Input: 570 mA @ 5V DC

Relay: 900 mA @ 30V DC, Class 2, 
resistive only

Power consumption, max

16.8 W

2 W

2 W

1.5 W

2.8 W

Power dissipation, max

8.8 W

2 W

2 W

1.5 W

2.8 W

Isolation voltage

N/A (SELV), functional insulation 
type, ContolNet to system

N/A (SELV), functional insulation 
type, ContolNet to system and 
between ControlNet channels

50V (continuous), basic insulation 
type, relay contacts to system

Wire size

0.21…3.3 mm

2

 (24…12 AWG) 

solid or stranded copper wire rated 
at 105 °C (221 °F) or greater, 1.2 
mm (3/64 in.) insulation max for 
power connections

NA

0.25…2.5 mm

2

 (22…14 AWG) 

solid or stranded copper wire rated 
at 75 °C (167 °F) or greater, 1.2 mm 
(3/64 in.) insulation max for power 
connections

Wiring category

2 - on power ports

2 - on ControlNet ports

2 - on ControlNet ports

2 - on relay ports

Enclosure type rating

None (open-style)

North American temp code

T5

T5

T5

T5

T4A

ATEX temp code

T5

T5

T5

T5

IECE x temp code

T5

T5

T5

T5

Resource

Description

ControlNet Modular Repeater Adapter Installation Instructions, publication 

1786-IN013

Installation instructions for 1786-RPA modular repeater adapters.

ControlNet Modular Repeater Short-distance Fiber Module Installation Instructions, publication 

1786-IN012

Installation instructions for 1786-RPFS repeater modules, short-distance fiber.

ControlNet Modular Repeater Medium-distance Fiber Module Installation Instructions, publicatio

1786-IN011

Installation instructions for 1786-RPFM repeater modules, medium-distance fiber.

ControlNet Fiber Ring Modules Installation Instructions, publication 

1786-IN003

Installation instructions for 1786-RPFRL and 1786-RPFRXL repeater modules, fiber ring

ControlNet Modular Repeater Dual Copper Module Installation Instructions, publication 

1786-IN001

Installation instructions for 1786-RPCD repeater modules,dual copper.

ControlNet Fiber Media Planning and Installation Guide, publicatio

CNET-IN001

Information about installing a ControlNet fiber media system.

ControlNet Coax Media Planning and Installation Guide, publicatio

CNET-IN002

Information about installing a ControlNet coaxial media system.

Industrial Automation Wiring and Grounding Guidelines, publication 

1770-4.1

 

General guidelines for installing a Rockwell Automation® industrial system.

Product Certifications website, 

http://www.rockwellautomation.com/products/certification

 

Declarations of conformity, certificates, and other certification details.