Allen-Bradley ControlNet 1786-RPCD Product Information Download Page 3

 

ControlNet Repeaters    

3

Rockwell Automation Publication 1786-PC001B-EN-P - January 2015

European Hazardous Location Approval

The following applies to products marked 

 II 3 G: Such modules:

•  Are Equipment Group II, Equipment Category 3, and comply with the Essential Health and Safety Requirements 

relating to the design and construction of such equipment given in Annex II to Directive 94/9/EC. See the EC 
Declaration of Conformity at 

http://www.rockwellautomation.com/products/certification

 for details.

•  The type of protection for the 1786-RPA and 1786-RPCD, is "Ex nA IIC T5 Gc" according to EN 60079-15 and comply to 

Standards: EN 60079-0:2012, EN 60079-15:2010, reference certificate number SIRA14ATEX4171X.

•  The type of protection for the 1786-RPFM and 1786-RPFS, is "Ex nA op is IIC T5 Gc" according to EN 60079-15 and 

comply to Standards: EN 60079-0:2012, EN 60079-15:2010, EN60079-28:2007, reference certificate number 
SIRA14ATEX4171X.

•  Are intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, or air are unlikely to 

occur, or are likely to occur only infrequently and for short periods. Such locations correspond to Zone 2 classification 
according to ATEX directive 1999/92/EC.  

IECEx Hazardous Location Approval

The following applies to products marked IECEx:

• Such modules are intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, or air are 

unlikely to occur, or are likely to occur only infrequently and for short periods. Such locations correspond to Zone 2 
classification to IECEx 60079-0.

• The type of protection for the 1786-RPA and 1786-RPCD, is "Ex nA IIC T5 Gc" according to IEC 60079-15.

The type of protection for the 1786-RPFM and 1786-RPFS, is "Ex nA op is IIC T5 Gc" according to IEC 60079-15.

• Such modules comply to Standards IIEC 60079-0:2011 Ed. 6, IEC 60079-15:2010 Ed. 4, IEC 60079-28:2007 Ed. 1.0, 

reference IECEx certificate number IECEx SIR 14.0048X. 

ATEX and IECEx Special Conditions for Safe Use

Mount the 1786-RPA/B Repeater Adapter Module

This section explains how to mount the 1786-RPA/B repeater adapter module.

Follow these steps to mount the 1786-RPA/B module.

1.Position the repeater adapter module on the 35 x 7.5 mm 
(1.4 x 0.3 in.) DIN rail (Allen-Bradley part number 199-DR1) 

at a 30

°

 angle.

2.Hook the lip on the rear of the 1786-RPA/B repeater 
adapter module onto the top of the DIN rail, and rotate the 
repeater adapter module onto the rail.

 

3. Press the repeater adapter module down onto the DIN rail until flush.

When the locking tab snaps into position, the repeater adapter module is locked to the DIN rail.

If the repeater adapter module does not snap into position, use a screwdriver or similar device to move the locking tab 
down while pressing the repeater adapter flush onto the DIN rail. 

4. Release the locking tab to lock the adapter in place. 

If necessary, push up on the locking tab to lock.

 

5. Once the repeater adapter module is attached to the DIN rail, slide the repeater modules to the left to mate with the 

repeater adapter module.

6. Attach the DIN rail locks to the left side of the repeater adapter module and the right side of the attached modules to 

lock the repeater adapter module and modules in place.

7. Repeat steps 1…6 for each of the two DIN rail locks.

8. Tighten the two screws on the DIN rail lock to a torque of 1.1 N•m (9…11 lb•in).

9. Wire the repeater adapter module.
10. Terminate any unused coax ports by connecting a 75 

Ω 

terminator to the unused BNC connector.

One 75 

Ω

 terminator is shipped with the repeater adapter module.

Wire the 1786-RPA/B Repeater Adapter Module

This section describes how to wire your module.

1. Make sure you have obtained the following items before you begin to wire the module:

•  Two lengths of 0.21…3.3 mm

2

 (24…12 AWG) wire

• Wire 

stripping 

tool

• Small, 

flathead 

screwdriver

2. Strip about 7 mm (0.28 in.) of insulation from the end of each wire.

ATEX and IECEx Hazardous Location Conformity

Model

Protection Type

ATEX Certificate

IECEx Certificate

1786-RPA

Ex nA IIC T5 Gc

Sira 14ATEX4171X

IECEx SIR 14.0048X

1786-RPCD

Ex nA IIC T5 Gc

Sira 14ATEX4171X

IECEx SIR 14.0048X

1786-RPFM

Ex nA op is IIC T5 Gc

Sira 14ATEX4171X

IECEx SIR 14.0048X

1786-RPFS

Ex nA op is IIC T5 Gc

Sira 14ATEX4171X

IECEx SIR 14.0048X

1786-RPFRL

1786-RPFRXL

WARNING: 

• This equipment is not resistant to sunlight or other sources of UV radiation.
• This equipment must be mounted in an ATEX/IECEx Zone 2 certified enclosure with a minimum ingress 

protection rating of at least IP54 (as defined in EN/IEC 60529) and used in an environment of not more 
than Pollution Degree 2 (as defined in EN/IEC 60664-1) when applied in Zone 2 environments. The 
enclosure must be accessible only by the use of a tool.

• This equipment must be used within its specified ratings defined by Rockwell Automation.
• Provision must be made to prevent the rated voltage from being exceeded by transient disturbances of 

more than 140% of the rated voltage when applied in Zone 2 environments.

• Secure any external connections that mate to this equipment by using screws, sliding latches, threaded 

connectors, or other means provided with this product.

• Do not disconnect equipment unless power has been removed or the area is known to be 

nonhazardous.

• When installed in a hazardous or non-hazardous area, the module must be installed in a 

suitably-certified (for example Ex e or Ex nA) enclosure providing a minimum ingress protection of IP54.

• When installed in a non-hazardous area, the module can alternatively be installed in a controlled 

environment that provides equivalent protection.

• The installer must verify that the service temperature of the suitably-certified enclosure and the 

‘maximum ambient’ temperature of the module when installed is not exceeded.

ATTENTION: 

This product is grounded through the DIN rail to chassis ground. Use zinc plated 

yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, 
aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent 
grounding. Secure DIN rail to mounting surface approximately every 200 mm (7.8 in.) and use end-anchors 
appropriately.

IMPORTANT

Horizontal mounting is preferred. We recommend that the 1786-RPA/B module be mounted at the top if 
vertical mounting is chosen.

WARNING: 

Removal and insertion under power (RIUP) is not supported. This module must be powered 

down while connecting and disconnecting it from any interconnected modules.
If you insert or remove the module while backplane power is on, an electrical arc can occur. This could cause 
an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.

ATTENTION: 

Make certain that the repeater adapter and modules are secured together with DIN rail locks 

on either side. Failure to do so can result in the loss of communication and/or cause damage to the modules.

IMPORTANT

The total number of modules that can be attached to the 1786-RPA/B repeater adapter cannot exceed 
four or the total power consumption of the modules cannot exceed 8 W or 1.6 A @ 5V DC, whichever 
comes first.
The 1786-RPFRL/B and 1786-RPFRXL/B modules require 570 mA each; therefore you can attach only two 
of these modules to a 1786-RPA/B repeater module. The maximum current draw at
5V DC is 400 mA for the 1786-RPFM module, 300 mA for the 1786-RPFS module, and 400 mA for the 
1786-RPCD module.
If you exceed the module or power limit, you can cause damage to the modules and repeater adapter.

IMPORTANT

For proper operation when using a 1786-RPFRXL/B module with a 1786-RPCD module attached to the 
same 1786-RPA/B repeater module, you must install any 1786-RPCD module to the left side of any 
1786-RPFRL or 1786-RPFRXL/B repeater module.

WARNING: 

An electrical arc can occur under the following circumstances: 

• when you connect or disconnect the removable terminal block (RTB) with field side power applied
• if you connect or disconnect the communications cable with power applied to this module or any device 

on the network

This could cause an explosion in hazardous location installations. Be sure that power is removed or the area 
is nonhazardous before proceeding.

Position the DIN rail lock to the DIN rail.

Press the DIN rail lock down 
onto the DIN rail.

Tighten the screws.