Allen-Bradley ControlNet 1786-RPCD Product Information Download Page 2

2

    ControlNet Repeaters

Rockwell Automation Publication 1786-PC001B-EN-P - January 2015

Environment and Enclosure

Prevent Electrostatic Discharge

Electrical Safety Considerations

Removal and Insertion Under Power (RIUP)

North American Hazardous Location Approval

The following information applies when operating this equipment in hazardous locations: Products marked “CL I, DIV 2, GP 
A, B, C, D” are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. 
Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. 
When combining products within a system, the most adverse temperature code (lowest “T” number) may be used to help 
determine the overall temperature code of the system. Combinations of equipment in your system are subject to 
investigation by the local authority having jurisdiction at the time of installation.

Informations sur l'utilisation de cet équipement en environnements dangereux:
Les produits marqués “CL I, DIV 2, GP A, B, C, D” ne conviennent qu'à une utilisation en environnements de Classe I Division 
2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque 
d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont 
combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être 
utilisé pour déterminer le code de température global du système. Les combinaisons d'équipements dans le système sont 
sujettes à inspection par les autorités locales qualifiées au moment de l'installation

ATTENTION: 

This equipment is intended for use in a Pollution Degree 2 industrial environment, in 

overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) 
without derating.
This equipment is not intended for use in residential environments and may not provide adequate 
protection to radio communication services in such environments.
This equipment is supplied as open-type equipment for indoor use. It must be mounted within an 
enclosure that is suitably designed for those specific environmental conditions that will be present and 
appropriately designed to prevent personal injury resulting from accessibility to live parts. The 
enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, 
complying with a flame spread rating of 5VA or be approved for the application if nonmetallic. The 
interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this 
publication may contain additional information regarding specific enclosure type ratings that are 
required to comply with certain product safety certifications.
In addition to this publication, see the following:
• Industrial Automation Wiring and Grounding Guidelines, publication 

1770-4.1

 , for additional 

installation requirements.

• NEMA Standard 250 and EN/IEC 60529, as applicable, for explanations of the degrees of protection 

provided by enclosures.

ATTENTION: 

• This product is grounded through the DIN rail to chassis ground. Use zinc plated yellow-chromate 

steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum 
or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent 
grounding. Secure DIN rail to mounting surface approximately every 200 mm (7.8 in.) and use 
end-anchors appropriately.

• If this equipment is used in a manner not specified by the manufacturer, the protection provided by 

the equipment may be impaired.

• Before installing, configuring, operating, or maintaining this product, read this document and the 

documents listed in the additional resources section for installing, configuring, or operating 
equipment. Users should familiarize themselves with installation and wiring instructions in addition 
to requirements of all applicable codes, laws, and standards.

• Installation, adjustments, putting into service, use, assembly, disassembly, and maintenance shall 

be carried out by suitably trained personnel in accordance with applicable code of practice. In case of 
malfunction or damage, no attempts at repair should be made. The module should be returned to 
the manufacturer for repair. Do not dismantle the module.

• This equipment is certified for use only within the surrounding air temperature range of 0…60 °C 

(32…140 °F). The equipment must not be used outside of this range.

• Solid state equipment has operational characteristics differing from those of electromechanical 

equipment. Safety Guidelines for the Application, Installation, and Maintenance of Solid State 
Controls, publication 

SGI-1.1

, available from your local Rockwell Automation sales office, or online at 

http://www.rockwellautomation.com/literature/

, describes some important differences between 

solid state equipment and hard-wired electromechanical devices.

• Use only a soft dry anti-static cloth to wipe down equipment. Do not use any cleaning agents.

ATTENTION: 

 For fiber modules

• Under certain conditions, viewing the optical port may expose the eye to hazard. When viewed 

under some conditions, the optical port may expose the eye beyond the maximum permissible 
exposure recommendations.

• 1786-RPFS, 1786-RPFS: Class 1 LED; optical radiation is present during operation.
• 1786-RPFRL, 1786-RPFRXL: Class 1 laser; laser radiation is present when the system is open and 

interlocks bypassed. Only trained and qualified personnel should be allowed to install, replace, or 
service this equipment.

• Do not discard the end cap. Use this end cap to cover the exposed interconnections on the last 

mounting base on the DIN rail. Failure to do so could result in equipment damage or injury from 
electric shock.

ATTENTION: 

This equipment is sensitive to electrostatic discharge, which can cause internal damage 

and affect normal operation. Follow these guidelines when you handle this equipment:
• Touch a grounded object to discharge potential static.
• Wear an approved grounding wrist strap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• Use a static-safe workstation, if available.
• Store the equipment in appropriate static-safe packaging when not in use.

ATTENTION: 

To comply with the CE Low Voltage Directive (LVD), all connections to this equipment 

must be powered from a source compliant with the following:
• Safety extra low voltage (SELV) supply
• Protected extra low voltage (PELV) supply

1786-RPA: To comply with UL/CUL requirements, this equipment must be powered from a source 
compliant with the following:
• IEC 60950-1 Ed. 2.1 , Clause 2.2  - SELV Circuits
• IEC 61010-2-201 Ed. 1, Clause 3.109  - PELV Circuits or Clause 3.110   - SELV Circuits
Do not wire more than two conductors on any single terminal.
Do not exceed 10 A on the power connector.

1786-RPFRL, 1786-RPFRXL: To comply with UL/CUL requirements, the relay connection must be 
powered from a source compliant with the following:
• Class 2 supply
• Limited voltage/current supply

WARNING: 

If you insert or remove the module while backplane power is on, an electrical arc can occur. 

This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.

WARNING: 

For applicable products, when you connect or disconnect the removable terminal block (RTB) 

with power applied, an electrical arc can occur. This could cause an explosion in hazardous location 
installations.
Be sure that power is removed or the area is nonhazardous before proceeding.

WARNING: 

For applicable products, if you connect or disconnect the communications cable with power 

applied to this module or any device on the network, an electrical arc can occur. This could cause an 
explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.

WARNING: 

For the 1786-RPA in hazardous location applications, use the supplied Phoenix MSTB 

2.5/2-STF-5.08 power terminal block.

WARNING: 

EXPLOSION HAZARD

• Do not disconnect equipment unless power has been removed or the area is known to be 

nonhazardous. 

• Do not disconnect connections to this equipment unless power has been removed or the area is known 

to be nonhazardous. Secure any external connections that mate to this equipment by using screws, 
sliding latches, threaded connectors, or other means provided with this product.

• Substitution of components may impair suitability for Class I, Division 2.
• If this product contains batteries, they must be changed only in an area known to be nonhazardous.

AVERTISSEMENT: 

RISQUE D'EXPLOSION

• Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher 

l'équipement.

• Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher les 

connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets 
coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.

• La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement 

de Classe I, Division 2.

• S'assurer que l'environnement est classé non dangereux avant de changer les piles.

Reviews: