    ControlNet Repeaters

Rockwell Automation Publication 1786-PC001B-EN-P - January 2015

3. Attach the V

in

 + wire to one of the V

in

 + terminals on the RTB. 

4. Tighten the screws to 0.6…0.8 N•m (5…7 lb•in).
5. Attach the V 

in

 - wire to one of the V 

in

 - terminals on the RTB.

6. Tighten the screws to 0.6…0.8 N•m (5…7 lb•in).

7. Install the RTB onto the repeater adapter module. 
8. Tighten the screws to 0.6…0.8 N•m (5…7 in•lb).
9. Connect the repeater adapter module to the ControlNet network by connecting the drop line of the coax tap to the BNC 

connector.

If the adapter has dual ports, connect both ports.

10. Terminate any unused coax ports by connecting a 75 W terminator to the unused BNC connector.

One 75 

Ω

 terminator is shipped with the repeater adapter module.

Connect a 1786-RPCD Dual Copper Repeater Module

If you need to connect only one coax channel on the 1786-RPCD module, you can use either channel 1 or channel 2. Both 
channels 1 and 2 operate identically and can be used interchangeably. Be sure to terminate the unused channel with a 
75

Ω

 terminating resistor (catalog number 1786-XT).

1. Connect the ControlNet tap to port #1.
2. Align the knob of the BNC cable connector with the locks of the BNC module connector, and insert the connector into 

channel 1.

3. Twist the BNC connector until the bayonet lug is locked into place.

4. To connect channel 2, repeat Step 1 for channel 2. If channel 2 is not used, connect a 75-

Ω

 

terminating resistor (catalog 

number 1786-XT) to the port labeled channel 2.

Connect a 1786-RPFS Fiber Module

This module requires a pre-terminated zipcord wiring kit. The kits are offered in a variety of lengths. Consult with your local 
distributor for attenuation specifications before you purchase your fiber media components.
The zipcord uses a duplex cable that contains two separate fibers, one for transmit and one for receive. If you are wiring 
only one channel, you can use either channel 1 or channel 2.
1. Remove protective caps from ports that require a connection and save the caps for future storage protection.
2. Hold down the latch and insert the channel 1 zipcord connector into the A and B connectors until the pins and latch lock 

into place.

Make certain you insert the blue pin, receive, of the zipcord connector in A and the black pin, transmit, into B.

3. Hold down the latch and insert the other end of the duplex cable into another module by using either channel 1 or 

channel 2 of the other module.

Connect a 1786-RPFM, 1786-RPFRL/B, 1786-RPFRXL/B Fiber Module

If you are wiring only one channel, you can use either channel 1 or channel 2. 
Follow these steps to connect to channel 1, receive (RX).
1. Remove protective caps from ports that require a connection, and save for future storage protection.
2. Align the knob of the cable connector with the groove of the module connector.
3. Insert the connector into channel 1 RX.

4. Twist the receive connector until the bayonet lug locks into place.
5. Repeat these steps to connect to channel 1, transmit (TX).

IMPORTANT

The unused V

in

 + and V

in

 - terminals can be used to supply power to other devices. However, the 

total current draw on daisy-chained power connections through any single 1786-RPA module 
cannot exceed 10 A.

 V

in

 + and V

in

 - Terminals 

31492-M

75 

Ω

terminator

Tap

BNC connector

IMPORTANT

The duplex cable is manufactured with the fiber reversed on opposite ends. This automatically 
connects channel A of one unit to channel B of the other. Do not connect more than one duplex fiber 
or two simplex fibers between the same modular repeaters, even if they are from different modules 
on the same repeater.

ATTENTION: 

Under certain conditions, viewing the optical port may expose the eye to hazard. When viewed 

under some conditions, the optical port may expose the eye beyond the maximum permissible exposure 
recommendations

ATTENTION: 

Under certain conditions, viewing the optical port may expose the eye to hazard. When 

viewed under some conditions, the optical port may expose the eye beyond the maximum permissible 
exposure recommendations.

IMPORTANT

Be certain the fiber cable you connect to channel 1 (receive) on one module is set to channel 1 (transmit) 
on the other module. You can use channel 1 or channel 2 on either module.

30079

Channel 1, A and B

Channel 2, A and B