Publication 1769-UM001B-EN-P - October 2002
3-10
Configuring Your Compact I/O Series A DeviceNet Adapter
4.
You may choose from the pull-down menu to change the
electronic keying to exact match, compatible module, or disable
keying.
•
Exact Match
: The programmed module type (e.g. 1769-IA16)
and the revision must match exactly with the actual module.
•
Compatible Module
: The programmed module type must
match the actual module, but the revision of the actual
module can be equal or greater than the programmed
revision.
•
Disable
: Any module may be used as a replacement.
Refer to the Comparison Feature section on page 3-22 for an
explanation on the use of this field.
5.
If desired, choose
Set for I/O Only
to automatically modify the
input/output data sizes to real time settings and the other
configuration data to their default values.
6.
If desired, choose
Data Description
to view the data definitions
of each input and output word assigned to the module.
7.
To remove specific words/functions, uncheck the appropriate
box and choose
OK
on the Data Description screen.
8.
To apply the specific words/functions, check the appropriate
box and choose
OK
on the Data Description screen.
9.
Once you’ve finished making your changes, you may choose
OK
from the I/O Module screen to return to the Bank
Configuration screen.
Summary of Contents for Compact I/O 1769-ADN DeviceNet
Page 1: ...Compact I O 1769 ADN DeviceNet Adapter 1769 ADN User Manual Allen Bradley...
Page 4: ......
Page 10: ...Publication 1769 UM001B EN P October 2002 vi Notes...
Page 24: ...Publication 1769 UM001B EN P October 2002 1 10 Installing Your DeviceNet Adapter Module Notes...
Page 152: ...Publication 1769 UM001B EN P October 2002 6 40 Application Examples Notes...
Page 158: ...Publication 1769 UM001B EN P October 2002 A 6 Specifications Notes...
Page 190: ...Publication 1769 UM001B EN P October 2002 B 32 Explicit Messaging Application Examples Notes...
Page 203: ...Publication 1769 UM001B EN P October 2002 5 Allen Bradley...