Publication 1769-UM001B-EN-P - October 2002
6-6
Application Examples
Configuring the 1747-SDN
To configure the 1747-SDN DeviceNet scanner to exchange I/O data
with the 1769-ADN, double-click on the 1747-SDN. You’ll see this
screen.
The General tab supplies information about the scanner. Choose the
Module tab and choose
Upload
on the Scanner Configuration screen.
Once the upload is complete you’ll return to the Module tab.
You should accept the defaults except for the 1747-SDN slot number.
For this example, the slot number for the 1747-SDN in its SLC chassis
is 3.
After modifying the chassis slot number, choose
Download to
Scanner
. This will ensure that the correct I/O addresses are displayed
under the Input and Output tabs.
Now choose the Scanlist tab. To add the 1769-ADN to the 1747-SDN
scanlist, choose the 1769-ADN shown in the Available Devices box on
the left. Choose the single right arrow between the Available Devices
box and the Scanlist box. This moves the 1769-ADN to the 1747-SDN
scanlist.
Summary of Contents for Compact I/O 1769-ADN DeviceNet
Page 1: ...Compact I O 1769 ADN DeviceNet Adapter 1769 ADN User Manual Allen Bradley...
Page 4: ......
Page 10: ...Publication 1769 UM001B EN P October 2002 vi Notes...
Page 24: ...Publication 1769 UM001B EN P October 2002 1 10 Installing Your DeviceNet Adapter Module Notes...
Page 152: ...Publication 1769 UM001B EN P October 2002 6 40 Application Examples Notes...
Page 158: ...Publication 1769 UM001B EN P October 2002 A 6 Specifications Notes...
Page 190: ...Publication 1769 UM001B EN P October 2002 B 32 Explicit Messaging Application Examples Notes...
Page 203: ...Publication 1769 UM001B EN P October 2002 5 Allen Bradley...