Publication 2364F-5.05 - March 1999
A-2
Reference Information
Table B: Electrical Specifications–Part 1
Nominal
Continuous
Maximum
Control Transformer Ratings
RGU
Current
Code
Input
Voltage
(V AC)
AC Line
Current
(A AC)
Input
Power
(kVA)
Nominal DC
Bus Voltage
(V DC)
Continuous DC
Bus Current
(A DC)
ô
Rated DC
Bus (kW)
Basic
Capacity
(kVA)
Standard
Capacity
(kVA)
J
380
77
51
564
85
49
2.0
5.0
K
380
182
120
564
200
116
2.0
5.0
L
380
330
217
564
363
211
2.0
5.0
M
380
678
447
564
746
433
5.0
5.0
N
380
906
596
564
997
578
5.0
10.0
J
460
77
61
683
85
59
2.0
5.0
K
460
182
145
683
201
141
2.0
5.0
L
460
330
263
683
364
255
2.0
5.0
M
460
678
541
683
749
524
5.0
5.0
N
460
906
722
683
1000
700
5.0
10.0
J
575
77
62
848
88
74
2.0
5.0
K
575
182
181
848
201
170
2.0
5.0
L
575
286
285
848
326
276
2.0
5.0
M
575
602
600
848
686
582
5.0
5.0
N
575
802
799
848
914
775
5.0
10.0
The continuous AC line current values apply to both motoring and regenerating operations.
ô
Rated DC bus kW is the power available on the DC thru bus at rated voltage and current.