Chapter 7
Configure Parameters
Table 28 - Default Settings of All Parameters
Parameter
Number
Parameter
Number
Parameter Name
Setting Range
Default Value
User Setting
Setting
Date
User
Parameters
U.000
Unit Selection
275…750V
750V
U.001
FWD Current Limit
0…150%
150%
U.002
REV Current Limit
0…150%
150%
Factory
Parameters
F.000
Password
0…999
0
F.001
Unit Selection
• 065.b
• 130.b
• 190.b
• 195.b
• 380.b
• 570.b
• 65 Amps
• 130 Amps
• 190 Amps
• 195 Amps
• 380 Amps
• 570 Amps
F.002
Rated Current
• 065.b: 10…70A
• 130.b: 20…140A
• 190.b: 30…210A
• 195.b: 30…215A
• 380.b: 60…430A
• 570.b: 90…645A
• 065.b: 65 Amps
• 130.b: 130 Amps
• 190.b: 190 Amps
• 195.b: 195 Amps
• 380.b: 380 Amps
• 570.b: 570 Amps
F.003
Current Control Proportional Gain
0.01…10.0 times
1.00 times
F.004
Current Control Integral Gain
1.0…3000 rad/s
64 rad/s
F.005
Voltage Control Proportional Gain
0.01…30.0 times
5.00 times
F.006
Voltage Control Integral Gain
1.0…3000 rad/s
128 rad/s
F.007
Bus Overvoltage Detection Level
325…900V
800V
F.008
Bus Low Voltage Detection Level
200…700V
400V
F.009
AC Overvoltage Detection Level
200…550V
550V
F.010
Carrier Frequency
5, 10, and 15 kHz
• 10 kHz: 8720MC-RPS065
• 5 kHz: 8720MC-RPS190
F.011
Deadtime
1.5…15.0 μs
6.0 μs
F.012
Allowable Time for Instantaneous Power Loss
0.05…3.00 s
0.50 s
F.013
AC Reactor Capacity
100…8,000 μH
See previous section
F.014
Precharge/Discharge Time
0.5…30.0 s
3.0 s
(3)
F.015
Wattage of Precharge/Discharge Resistor
50…2,000 W
See previous section
F.016
DC Bus Voltage Offset
(1)
0.900…1.100
1.000
F.017
Discharge Function Enable
OFF, ON
ON
F.018
Version Information
–
–
F.019
Selecting of Wiring Error (LE) Detecting Function
(2)
OFF, ON
ON
(1) These parameters are available from only software version 2.00 or later.
(2) This parameter is available only from software version 3.00 or later.
(3) This parameter must be set to 15.0 seconds for the 8720MC-RPS190 unit.