Rockwell Automation Publication 2711P-IN026H-EN-P - May 2018
17
High-bright Display Modules
Connect DC Power
Follow these steps to connect the terminal DC power.
1. Verify that the terminal is not connected to a power source.
2. Secure the DC power wires to the terminal block.
Follow the markings on the terminal blocks and the terminal for proper connections.
3. Secure the earth/ground wire to the earth/ground terminal screw at the bottom of the
display.
DC Power Supply Connections
Ethernet Cable
For PanelView Plus 700 to 1500 terminals, use Belden 7921A shielded Ethernet Category 5e
cable according to TIA 568-B.1 and RJ45 connector according to IEC 60603-7 for compliance
with the European Union 89/336/EEC EMC Directive.
WARNING:
Explosion Hazard
Do not disconnect equipment unless power has been switched off and the area is known to be
nonhazardous.
Disconnect all power before installing or replacing components. Failure to disconnect power may
result in electrical shock or damage to the terminal.
Three-position Terminal Block
(Series A to D logic modules)
Two-position Terminal Block
(Series E or later logic modules)
Earth/Ground to Ground Bus
DC-
DC-
DC+
DC+
GND