High-bright Display Modules
On most PanelView Plus devices, the earth/ground terminal is internally connected to the DC-
terminal within the product.
The PanelView Plus devices have isolated and nonisolated communication ports.
For more information refer to the PanelView Plus Terminals User Manual, publication
2711P-
UM001
.
Remove and Install the Power Terminal Block
The terminals ship with a power terminal block installed. You can remove and reinstall the
terminal block for ease of installation, wiring, and maintenance.
• Series A to D, DC logic modules use a three-position terminal block.
• Series E or later, DC logic modules use a two-position terminal block.
Follow these steps to remove the terminal block.
1. Loosen the two screws that secure the terminal block.
ATTENTION:
Damage or malfunction can occur when a voltage potential exists between two
separate ground points. Make sure the terminal does not serve as a conductive path between
ground points at different potentials.
WARNING:
Explosion Hazard
• Substitution of components may impair suitability for hazardous locations.
• Do not disconnect equipment unless power has been switched off and area is known to be
nonhazardous.
• Do not connect or disconnect components unless power has been switched off.
• All wiring must comply with N.E.C. articles 501, 502, 503, and/or C.E.C. section 18-1J2 as
appropriate.
• Peripheral equipment must be suitable for the location in which it is used.
ATTENTION:
Disconnect all power before installing or replacing components. Failure to disconnect
power may result in electrical shock or damage to the terminal.