Data Highway Message Set
Chapter 8
814
Table 8.D
Status Information (in Hex) Received from a 1779KFM Interface
Byte
Bit
Value
Meaning
1
Not Used
Processor Type
2
07
FE
Computer/Synchronous Device
Interface Type
3
07
15
1779KFM Interface
47
Not Used
Diagnostic
Counters
8
9
07
07
Bytes 8 and 9 contain the starting byte address of
diagnostic counters.
Revision and
Series Level of
the 1779KFM
10
04
0
1
Revision A
Revision B
Etc.
57
0
1
Series A
Series B
Etc.
Communication
Parameters
11
02
2
4
6
8
A
C
9,600 bits/second
19,200 bits/second
38,400 bits/second
57,600 bits/second
76,800 bits/second
115,200 bits/second
36
Not Used
7
0
1
Internal Clock ST
External Clock TT
12
2
0
1
When initiate network parameter change is
enabled.
When initiate network parameter change is
disabled.
4
0
1
When accept network parameter change is
enabled.
When accept network parameter change is
disabled.
Mode
13
0, 1
Not Used
2
0
1
Execute Diagnostic Commands
Pass Diagnostic Commands through to Host Device
3, 4
Not Used
57
1
3
5
PAD Mode
Native Mode
Supervisory Mode
1416
Reserved