ATTENTION:  Remove power from the 1771 I/O chassis
backplane and wiring arm before removing or installing an 
I/O module.

Failure to remove power from the backplane or field wiring
arm could cause module damage, degradation of
performance, 
or injury.

Failure to remove power from the backplane could cause
injury or equipment damage due to possible unexpected
operation.

1.

Turn off power to the I/O chassis.

2.

Place the module in the plastic tracks on the top and bottom of the
slot that guides the module into position.

3.

Do not force the module into its backplane connector. Apply firm,
even pressure on the module to seat it properly.

4.

Secure the module’s position by doing the following:

with a Series A chassis, snap the chassis latch over the top of the
module

with a Series B chassis, pull down the locking bar

5.

Connect the field wiring arm to the input module.

Connecting Wiring to the Input Module

Connect wiring to the input module using the field wiring arm (cat. no.
1771-WH) shipped with the module (shown in the connection diagram
below). Make your connections as follows:

1.

Attach the field wiring arm to the pivot bar on the bottom of the I/O chassis.

2.

Pivot the wiring arm upward and push it into the module until the wiring
arm clicks into position. The field wiring arm is designed to let you  install
and remove the module without disconnecting the wires.

ATTENTION:  Do not apply ac or reverse dc voltage to
module terminals. Circuitry at the input of module may 
be damaged.

Summary of Contents for 1771-IGD

Page 1: ...w and 2 0V dc to 5 25V dc high This module contains input filtering to limit the effects of voltage transients caused by contact bounce and or radiated electrical noise The delay due to filtering is less than 1ms For maximum noise immunity the output of the TTL device should have a pull up resistor of 1k ohm typical Add an external pull up resistor to the output terminals of the device if necessar...

Page 2: ...r damage the module Observe the following precautions to guard against electrostatic damage Wear an approved wrist strap grounding device or touch a grounded object to discharge yourself before handling the module Do not touch the backplane connector or connector pins If you configure or replace internal components do not touch other circuit components inside the module If available use a static f...

Page 3: ... to key the I O slots to accept only this type of module The module circuit board is slotted in two places on the rear edge The position of the keying bands on the backplane connector must correspond to these slots to allow insertion of the module You can key any connector in an I O chassis to receive this module except for the left most connector reserved for adapter or processor modules Place ke...

Page 4: ...ule to seat it properly 4 Secure the module s position by doing the following with a Series A chassis snap the chassis latch over the top of the module with a Series B chassis pull down the locking bar 5 Connect the field wiring arm to the input module Connecting Wiring to the Input Module Connect wiring to the input module using the field wiring arm cat no 1771 WH shipped with the module shown in...

Page 5: ...il shield Twist the foil shield and drain wire together to form a single strand Attach a ground lug 20104 Belden 8761 Cable 5 Ground the single strand at the ground lug end to the grounding stud on the I O chassis or by using single point grounding 19480 When you connect grounding conductors to the I O chassis grounding stud place a star washer under the first lug then place a nut with captive loc...

Page 6: ...ll up resistor 1K ohm typical See applicable codes and laws Input 10 Input 11 Input 12 Input 13 Input 14 Input 15 Input 16 Input 17 5V dc 5V dc 5V dc Actual wiring runs in this direction A B C D 00 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17 E 10450 I 1 1 You can make this connection to terminal A B C or D Field Wiring Arm Cat No 1771 WH 7 Connect TTL output devices using Belden 8761 shielded cab...

Page 7: ...ors red HIGH Positive Logic Indicator green 10451 I To replace a blown fuse proceed as follows ATTENTION Remove power from the 1771 I O chassis backplane and field wiring arm before removing or installing an I O module Failure to remove power from the backplane or field wiring arm could cause module damage degradation of performance or injury Failure to remove power from the backplane could cause ...

Page 8: ...lication 1770 4 1 Programmable Controller Wiring and Grounding Guidelines With major offices worldwide Algeria Argentina Australia Austria Bahrain Belgium Brazil Bulgaria Canada Chile China PRC Colombia Costa Rica Croatia Cyprus Czech Republic Denmark Ecuador Egypt El Salvador Finland France Germany Greece Guatemala Honduras Hong Kong Hungary Iceland India Indonesia Israel Italy Jamaica Japan Jord...