background image

TTL Input Module

Cat. No. 1771IGD

Installation Instructions

3

You select high-true or low-true using the jumper accessible through a slot
at the top of the module.

1.

Locate the jumper in the slot at the top edge of the module.

2.

Use tweezers to position the jumper as required for your application.

When on front 2 pins, negative logic 

selected (low = true).

TTL Input Module

When on rear 2 pins, positive logic

selected (high = true).

10449I

TTL Logic Level Selection Jumper Assembly

Keying Your I/O Chassis

Use the plastic keying bands, shipped with each I/O chassis, to key the I/O
slots to accept only this type of module.

The module circuit board is slotted in two places on the rear edge. The
position of the keying bands on the backplane connector must correspond
to these slots to allow insertion of the module. You can key any connector
in an I/O chassis to receive this module except for the left-most connector
reserved for adapter or processor modules. Place keying bands between the
following numbers labeled on the upper backplane connector:

Between 16 and 18
Between 24 and 26

You can change the position of these keys if system redesign and rewiring
makes insertion of a different module necessary.

Installing the Input Module

To install the TTL input module in your 1771 I/O chassis, follow the steps
listed below.

Summary of Contents for 1771-IGD

Page 1: ...w and 2 0V dc to 5 25V dc high This module contains input filtering to limit the effects of voltage transients caused by contact bounce and or radiated electrical noise The delay due to filtering is less than 1ms For maximum noise immunity the output of the TTL device should have a pull up resistor of 1k ohm typical Add an external pull up resistor to the output terminals of the device if necessar...

Page 2: ...r damage the module Observe the following precautions to guard against electrostatic damage Wear an approved wrist strap grounding device or touch a grounded object to discharge yourself before handling the module Do not touch the backplane connector or connector pins If you configure or replace internal components do not touch other circuit components inside the module If available use a static f...

Page 3: ... to key the I O slots to accept only this type of module The module circuit board is slotted in two places on the rear edge The position of the keying bands on the backplane connector must correspond to these slots to allow insertion of the module You can key any connector in an I O chassis to receive this module except for the left most connector reserved for adapter or processor modules Place ke...

Page 4: ...ule to seat it properly 4 Secure the module s position by doing the following with a Series A chassis snap the chassis latch over the top of the module with a Series B chassis pull down the locking bar 5 Connect the field wiring arm to the input module Connecting Wiring to the Input Module Connect wiring to the input module using the field wiring arm cat no 1771 WH shipped with the module shown in...

Page 5: ...il shield Twist the foil shield and drain wire together to form a single strand Attach a ground lug 20104 Belden 8761 Cable 5 Ground the single strand at the ground lug end to the grounding stud on the I O chassis or by using single point grounding 19480 When you connect grounding conductors to the I O chassis grounding stud place a star washer under the first lug then place a nut with captive loc...

Page 6: ...ll up resistor 1K ohm typical See applicable codes and laws Input 10 Input 11 Input 12 Input 13 Input 14 Input 15 Input 16 Input 17 5V dc 5V dc 5V dc Actual wiring runs in this direction A B C D 00 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17 E 10450 I 1 1 You can make this connection to terminal A B C or D Field Wiring Arm Cat No 1771 WH 7 Connect TTL output devices using Belden 8761 shielded cab...

Page 7: ...ors red HIGH Positive Logic Indicator green 10451 I To replace a blown fuse proceed as follows ATTENTION Remove power from the 1771 I O chassis backplane and field wiring arm before removing or installing an I O module Failure to remove power from the backplane or field wiring arm could cause module damage degradation of performance or injury Failure to remove power from the backplane could cause ...

Page 8: ...lication 1770 4 1 Programmable Controller Wiring and Grounding Guidelines With major offices worldwide Algeria Argentina Australia Austria Bahrain Belgium Brazil Bulgaria Canada Chile China PRC Colombia Costa Rica Croatia Cyprus Czech Republic Denmark Ecuador Egypt El Salvador Finland France Germany Greece Guatemala Honduras Hong Kong Hungary Iceland India Indonesia Israel Italy Jamaica Japan Jord...