        Direct Communication Module     

Publication 1747-IN005B-EN-P - March 2003

Starting I/O Group Number (SW1-7 and SW1-8)

The starting I/O group number must be an even number from 0 to 6 (e.g. 0, 2, 4, or 
6) and is dependent upon whether the 1747-DCM has been configured as a full, ¾, 
½, or ¼ chassis. The first word transferred is always the status word for the 
1747-DCM.

The table below shows the switch settings for the starting I/O group numbers.

DIP Switch 2 Settings

The default settings are shown below.

Data Rate (SW2-1 and SW2-2)

Starting I/O Group Number

SW1-7

SW1-8

Valid Chassis Configuration

0

ON

ON

All

2

ON

OFF

¾, ½, ¼

4

OFF

ON

½,  ¼

6

OFF

OFF

¼

Data Rate

SW2-1

SW2-2

Cable Length (Belden 9463)

57.6K baud

ON

ON

3048 meters (10,000 feet)

115.2K baud

ON

OFF

1542 meters (5,000 feet)

230.4K baud

OFF

ON

762 meters (2,500 feet)

OFF

OFF

O

N

 8

12

3

4

5

6

7

Reserved

Rack Size
Last Rack

Clear On Fault

Data Rate

Summary of Contents for 1747-DCM

Page 1: ...ication Module Catalog Number 1747 DCM Inside page For More Information 3 Hazardous Location Considerations 4 Environments dangereux 4 System Overview 5 Hardware Features 6 Module Configuration 7 Inst...

Page 2: ...lication SGI 1 1 Safety Guidelines for the Application Installation and Maintenance of Solid State Control available from your local Rockwell Automation office describes some important differences bet...

Page 3: ...printed manual by contacting your local distributor or Rockwell Automation representative visiting www theautomationbookstore com calling 1 800 963 9548 USA Canada or 001 330 725 1574 Outside USA Can...

Page 4: ...nnements dangereux WARNING EXPLOSION HAZARD Substitution of components may impair suitability for Class I Division 2 Do not replace components or disconnect equipment unless power has been switched of...

Page 5: ...these supervisory processors to transfer data between one another The 1747 DCM appears as an RIO adapter to a PLC processor with integral RIO scanner on the RIO Communication Link an RIO scanner catal...

Page 6: ...00 CAT SERIAL NO DCM DIRECT COMMUNICATION MADE IN USA COMM FAULT CONFIGURATION RACK SIZE 1 4 1 2 3 4 1 RACK ADDR FIRST I O GROUP 0 2 4 6 DATA RATE K B S 57 6 115 2 230 4 LINE 1 _______ SHIELD ______ L...

Page 7: ...ible chassis address choices for all scanners To use this table first determine which of the following categories applies to your scanner PLC 2 mini PLCs PLC 2 30 with 1770 SD SD2 remote scanner PLC 3...

Page 8: ...F 12 12 12 12 ON ON OFF ON OFF ON 13 13 13 13 ON ON OFF ON OFF OFF 14 14 14 14 ON ON OFF OFF ON ON 15 15 15 15 ON ON OFF OFF ON OFF 16 16 16 16 ON ON OFF OFF OFF ON 17 17 17 17 ON ON OFF OFF OFF OFF 2...

Page 9: ...60 OFF OFF ON ON ON ON 61 OFF OFF ON ON ON OFF 62 OFF OFF ON ON OFF ON 63 OFF OFF ON ON OFF OFF 64 OFF OFF ON OFF ON ON 65 OFF OFF ON OFF ON OFF 66 OFF OFF ON OFF OFF ON 67 OFF OFF ON OFF OFF OFF 70 O...

Page 10: ...the 1747 DCM The table below shows the switch settings for the starting I O group numbers DIP Switch 2 Settings The default settings are shown below Data Rate SW2 1 and SW2 2 Starting I O Group Number...

Page 11: ...data bits in their last state if an RIO communication failure occurs or when the supervisory processor enters the Program Test Fault mode Last Chassis SW2 4 Switch SW2 4 must be set to the OFF positi...

Page 12: ...which I O module is in the second slot See Discrete Input and Output Modules Technical Data publication number 1746 2 35 for details Chassis Size SW2 5 SW2 6 Number of RIO Words Transferred Total Wor...

Page 13: ...bottom latches are latched 4 Attach the RIO link cable to the connector on the front of the module 5 Insert the cable tie in the slots 6 Route the cable down and away from the module securing it with...

Page 14: ...ey Red Black Gold 762 m 2 500 ft Without Extended Node Capability 57 6K baud 150 Watt 3048 m 10 000 ft 115 2K baud 150 Watt Brown Green Brown Gold 1524 m 5 000 ft 230 4K baud 82 Watt Grey Red Black Go...

Page 15: ...ng group 6 causes a configuration error Off Normal State No action required If LED is Cause Corrective Action On Normal State No action required Flashing RIO scanner s processor in Program Test Fault...

Page 16: ...ifications Backplane Current Consumption 360 mA at 5V dc Operating Temperature 0 C to 60 C 32 F to 140 F Storage Temperature 40 C to 85 C 40 F to 185 F Humidity Rating 5 to 95 non condensing Agency Ce...

Reviews: