background image

6

        Direct Communication Module     

Publication 1747-IN005B-EN-P - March 2003

Extended Node Capability

The 1747-DCM features extended node capability. Extended node capability allows 
you to have up to 32 adapters on the RIO link using an 82

 termination resistor at 

both ends of the RIO link for all baud rates.

Hardware Features

IMPORTANT

Extended node capability can only be used if the scanner and all 
adapters on the RIO link have extended node capability.

SLC 500

CA
T

SERIAL

 NO.

DCM

DIRECT COMMUNICA

TION

MADE IN USA

COMM

FAULT

CONFIGURATION

RACK SIZE

1/4  1/2  3/4  1

RACK ADDR

FIRST I/O GROUP

0       2       4       6

DATA RATE (K B/S)

57.6   115.2    230.4

LINE 1 _______

SHIELD ______

LINE 2 _______

MODULE

8

7

6

5

4

3

2

1

8

7

6

5

4

3

2

1

I/O

GROUP

(LSB)

(MSB)

X

X

RACK

SIZE

LAST RACK

CLR ON FLT

DATA

RATE

SW 2

SW 1

SW1

SW2

 1

2

34567

8

 1

2

34567

8

RACK

ADDR

1747±DCM

SW2

SW1

O

N

 1

2

3

4

567

8

O

N

 1

234

5

6

7

8

I/O

GROUP

(LSB)

RACK

ADDRESS

(MSB)

RACK

SIZE

DATA
RATE

X
X

LAST RACK

CLR ON FLT

FAULT LED (Red)

COMM LED (Green)

Door Label

Front Label

RIO Link Connector

Cable Tie Slots

Self-Locking Tab

Side Label

DIP Switches

Self-Locking Tab

Summary of Contents for 1747-DCM

Page 1: ...ication Module Catalog Number 1747 DCM Inside page For More Information 3 Hazardous Location Considerations 4 Environments dangereux 4 System Overview 5 Hardware Features 6 Module Configuration 7 Inst...

Page 2: ...lication SGI 1 1 Safety Guidelines for the Application Installation and Maintenance of Solid State Control available from your local Rockwell Automation office describes some important differences bet...

Page 3: ...printed manual by contacting your local distributor or Rockwell Automation representative visiting www theautomationbookstore com calling 1 800 963 9548 USA Canada or 001 330 725 1574 Outside USA Can...

Page 4: ...nnements dangereux WARNING EXPLOSION HAZARD Substitution of components may impair suitability for Class I Division 2 Do not replace components or disconnect equipment unless power has been switched of...

Page 5: ...these supervisory processors to transfer data between one another The 1747 DCM appears as an RIO adapter to a PLC processor with integral RIO scanner on the RIO Communication Link an RIO scanner catal...

Page 6: ...00 CAT SERIAL NO DCM DIRECT COMMUNICATION MADE IN USA COMM FAULT CONFIGURATION RACK SIZE 1 4 1 2 3 4 1 RACK ADDR FIRST I O GROUP 0 2 4 6 DATA RATE K B S 57 6 115 2 230 4 LINE 1 _______ SHIELD ______ L...

Page 7: ...ible chassis address choices for all scanners To use this table first determine which of the following categories applies to your scanner PLC 2 mini PLCs PLC 2 30 with 1770 SD SD2 remote scanner PLC 3...

Page 8: ...F 12 12 12 12 ON ON OFF ON OFF ON 13 13 13 13 ON ON OFF ON OFF OFF 14 14 14 14 ON ON OFF OFF ON ON 15 15 15 15 ON ON OFF OFF ON OFF 16 16 16 16 ON ON OFF OFF OFF ON 17 17 17 17 ON ON OFF OFF OFF OFF 2...

Page 9: ...60 OFF OFF ON ON ON ON 61 OFF OFF ON ON ON OFF 62 OFF OFF ON ON OFF ON 63 OFF OFF ON ON OFF OFF 64 OFF OFF ON OFF ON ON 65 OFF OFF ON OFF ON OFF 66 OFF OFF ON OFF OFF ON 67 OFF OFF ON OFF OFF OFF 70 O...

Page 10: ...the 1747 DCM The table below shows the switch settings for the starting I O group numbers DIP Switch 2 Settings The default settings are shown below Data Rate SW2 1 and SW2 2 Starting I O Group Number...

Page 11: ...data bits in their last state if an RIO communication failure occurs or when the supervisory processor enters the Program Test Fault mode Last Chassis SW2 4 Switch SW2 4 must be set to the OFF positi...

Page 12: ...which I O module is in the second slot See Discrete Input and Output Modules Technical Data publication number 1746 2 35 for details Chassis Size SW2 5 SW2 6 Number of RIO Words Transferred Total Wor...

Page 13: ...bottom latches are latched 4 Attach the RIO link cable to the connector on the front of the module 5 Insert the cable tie in the slots 6 Route the cable down and away from the module securing it with...

Page 14: ...ey Red Black Gold 762 m 2 500 ft Without Extended Node Capability 57 6K baud 150 Watt 3048 m 10 000 ft 115 2K baud 150 Watt Brown Green Brown Gold 1524 m 5 000 ft 230 4K baud 82 Watt Grey Red Black Go...

Page 15: ...ng group 6 causes a configuration error Off Normal State No action required If LED is Cause Corrective Action On Normal State No action required Flashing RIO scanner s processor in Program Test Fault...

Page 16: ...ifications Backplane Current Consumption 360 mA at 5V dc Operating Temperature 0 C to 60 C 32 F to 140 F Storage Temperature 40 C to 85 C 40 F to 185 F Humidity Rating 5 to 95 non condensing Agency Ce...

Reviews: