All parameters are specified at 48V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM043A-EN-P — March 2014
5
Bulletin 1606 Switched Mode Power Supplies
4. DC-Input
Do not operate this power supply with DC-input voltage. Use the 1606-XLE480FP-D instead.
5. Input Inrush Current
An active inrush limitation circuit limits the input inrush current after turn-on of the input voltage and after short
input voltage interruptions.
The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on.
AC 100V
AC 120V
AC 230V
Inrush current
*)
max.
13A
peak
13A
peak
13A
peak
temperature
independent
typ.
11A
peak
9A
peak
7A
peak
temperature
independent
Inrush energy
*)
max.
2A
2
s 2.5A
2
s 0.5A
2
s temperature
independent
Inrush delay
typ.
940ms
940ms
740ms
start-up delay plus rise time
*)
Mains interruptions > 500ms
Fig. 5-1
Typical input inrush current
behavior at nominal load and 25°C ambient