All parameters are specified at 48V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

Rockwell Automation Publication 1606-RM043A-EN-P — March 2014

13

Bulletin 1606 Switched Mode Power Supplies

 

14. EMC 

The power supply is suitable for applications in industrial environment as well as in residential, commercial and light 
industry environment without any restrictions. A detailed EMC report is available upon request. 

 

EMC Immunity 

According generic standards: EN 61000-6-1 and EN 61000-6-2 

Electrostatic discharge  

EN 61000-4-2 

contact discharge 
air discharge 

8kV 
15kV 

Criterion A 
Criterion A 

Electromagnetic RF field 

EN 61000-4-3 

80MHz-2.7GHz 

20V/m 

Criterion A 

Fast transients (Burst) 

EN 61000-4-4 

input lines 
output lines 
DC-OK signal (coupling clamp) 

4kV 
2kV 
2kV 

Criterion A 
Criterion A 
Criterion A 

Surge voltage on input 

EN 61000-4-5 

L   N 
L   PE, N   PE 

2kV 
4kV 

Criterion A 
Criterion A 

Surge voltage on output 

EN 61000-4-5 

+   - 
+ / -   PE 

1kV 
2kV 

Criterion A 
Criterion A 

Surge voltage on DC-OK 

EN 61000-4-5 

DC-OK signal   PE 

1kV 

Criterion A 

Conducted disturbance 

EN 61000-4-6 

0.15-80MHz 

20V 

Criterion A 

Mains voltage dips 

EN 61000-4-11 

0% of 100Vac 
40% of 100Vac 
70% of 100Vac 
0% of 200Vac

 

40% of 200Vac 
70% of 200Vac 

0Vac, 20ms 
40Vac, 200ms 
70Vac, 500ms 
0Vac, 20ms 
80Vac, 200ms 
140Vac, 500ms 

Criterion A 
Criterion C  
Criterion A 
Criterion A 
Criterion A 
Criterion A 

Voltage interruptions 

EN 61000-4-11 

0% of 200Vac (=0V) 

5000ms 

Criterion C 

Voltage sags 

SEMI F47 0706 

dips on the input voltage according to SEMI F47 standard 

  

80% 

of 

120Vac 

(96Vac) 

70% of 120Vac (84Vac)

 

50% of 120Vac (60Vac) 

1000ms 
500ms 
200ms 

Criterion A 
Criterion A 
Criterion A 

Powerful transients 

VDE 0160 

over entire load range 

750V, 1.3ms 

Criterion A 

Criteria:

 

A:

    Power supply shows normal operation behavior within the defined limits.  

C:

    Temporary loss of function is possible. Power supply may shut down and restart by itself. The power supply will incur no damage or 

hazard. 

 

EMC Emission 

According generic standards: EN 61000-6-3 and EN 61000-6-4 

Conducted emission  
input lines 

EN 55011, EN 55022, FCC Part 15, CISPR 11, CISPR 22 

Class B 

Conducted emission  
output lines

**)

 

IEC/CISPR 16-1-2, IEC/CISPR 16-2-1 

limits for DC power port 
according EN 61000-6-3 fulfilled 

Radiated emission 

EN 55011, EN 55022 

Class B 

Harmonic input current 

EN 61000-3-2 

fulfilled for class A equipment 

Voltage fluctuations, flicker 

EN 61000-3-3 

fulfilled

*)

 

This device complies with FCC Part 15 rules. 
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this 
device must accept any interference received, including interference that may cause undesired operation. 

*)   tested with constant current loads, non pulsing 
**)  for information only, not mandatory for EN 61000-6-3 

Summary of Contents for 1606-XLC

Page 1: ...22 22 8 Inductive and Capacitive Loads 22 22 9 Charging Batteries 23 22 10 Operation on Two Phases 23 22 11 Use in a Tightly Sealed Enclosure 23 22 12 Mounting Orientations 24 PE and symbol PE is the...

Page 2: ...usly at temperatures up to 45 C Additionally the 1606 XLE480FP can deliver about 4 times the nominal output current for 15ms which helps to trip fuses on faulty output branches High immunity to transi...

Page 3: ...uct airflow and do not cover ventilation grid e g cable conduits by more than 30 Keep the following installation clearances 40mm on top 20mm on the bottom 5mm on the left and right sides are recommend...

Page 4: ...33A at 48V 10A see Fig 3 3 Power factor typ 0 99 0 99 0 95 at 48V 10A see Fig 3 4 Crest factor typ 1 5 1 5 1 65 at 48V 10A Start up delay typ 850ms 850ms 650ms see Fig 3 2 Rise time typ 90ms 90ms 90ms...

Page 5: ...he input inrush current after turn on of the input voltage and after short input voltage interruptions The charging current into EMI suppression capacitors is disregarded in the first microseconds aft...

Page 6: ...nom 480W continuously available nom 576W Power Boost Overload behaviour cont current output voltage 25Vdc see Fig 6 1 HiccupPLUS mode output voltage 25Vdc see Fig 6 1 Short circuit current min 18A loa...

Page 7: ...24 56V 32 40 48 20A 7 5 2 5 5 10 15 17 5 Adjustment Range Output Current Continuous current Factory setting Hiccup mode Output Voltage Parallel Use typ 42V 0 4 8 44V 46V 48V 56V 50V 52V 54V 12A 10 6 2...

Page 8: ...48V 10A min 5 Hold up Time Zero Transition Output Voltage Input Voltage 8 DC OK Relay Contact This feature monitors the output voltage which is produced by the power supply itself It is independent o...

Page 9: ...mption for a typical application where the power supply is loaded with 25 of the nominal load for 25 of the time 50 of the nominal load for another 25 of the time 75 of the nominal load for another 25...

Page 10: ...the built in electrolytic capacitors Lifetime expectancy is specified in operational hours and is calculated according to the capacitor s manufacturer specification The manufacturer of the electrolyt...

Page 11: ...t applicable Instructions a Use appropriate copper cables that are designed for minimum operating temperatures of 60 C for ambient up to 45 C and 75 C for ambient up to 60 C minimum 90 C for ambient u...

Page 12: ...t the output voltage Factory set 48 0V D DC OK LED green On when the output voltage is 90 of the adjusted output voltage E DC OK Relay Contact quick connect spring clamp terminals The DC OK relay cont...

Page 13: ...0Vac 200ms 140Vac 500ms Criterion A Criterion C Criterion A Criterion A Criterion A Criterion A Voltage interruptions EN 61000 4 11 0 of 200Vac 0V 5000ms Criterion C Voltage sags SEMI F47 0706 dips on...

Page 14: ...reduce output power or ambient temperature see Fig 15 2 IEC 62103 EN 50178 overvoltage category II Altitude de rating 30W 1000m or 5 C 1000m 2000m 6500ft see Fig 15 2 Over voltage category III IEC 62...

Page 15: ...rews small parts Over temperature protection yes Output shut down with automatic restart Input transient protection MOV Metal Oxide Varistor Internal input fuse included not user replaceable In case o...

Page 16: ...ions in which a load starts unexpectedly or cannot be switched off when unnoticed ground faults occur B When testing input to DC OK ensure that the max voltage between DC OK and the output is not exce...

Page 17: ...17 Bulletin 1606 Switched Mode Power Supplies 20 Physical Dimensions and Weight Weight 1000g 2 2lb DIN Rail Use 35mm DIN rails according to EN 60715 or EN 50022 with a height of 7 5 or 15mm The DIN r...

Page 18: ...s run in time unless noted otherwise 18 Rockwell Automation Publication 1606 RM043A EN P March 2014 Bulletin 1606 Switched Mode Power Supplies 21 Accessories 21 1 1606 XLC Wall Mounting Bracket This b...

Page 19: ...r and the built in large sized output capacitors of the power supply The capacitors get discharged during such an event which causes a voltage dip on the output The following two examples show typical...

Page 20: ...ed the wiring is considered as thermally safe wether the MCB opens or not To avoid voltage dips and under voltage situations in adjacent 48V branches which are supplied by the same source a fast magne...

Page 21: ...higher than the current of one unit Keep an installation clearance of 15mm left right between two power supplies and avoid installing the power supplies on top of each other Do not use power supplies...

Page 22: ...when the sum of the output voltage is above 60Vdc Avoid return voltage e g from a decelerating motor or battery which is applied to the output terminals Keep an installation clearance of 15mm left ri...

Page 23: ...urrent is typ 7mA when the power supply is switched off except if using a blocking diode 22 10 Operation on Two Phases 240V 10 max L2 L1 L3 L N PE Power Supply AC DC internal fuse The power supply can...

Page 24: ...urrent Curve A2 Max allowed output current results in approximately half the lifetime expectancy of A1 Fig 22 4 Mounting Orientation A Standard orientation Power Supply OUTPUT INPUT Output Current 0 1...

Page 25: ......

Page 26: ...ial help in getting your product up and running New Product Satisfaction Return Rockwell Automation tests all of its products to help ensure that they are fully operational when shipped from the manuf...

Reviews: