All parameters are specified at 48V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
14
Rockwell Automation Publication 1606-RM043A-EN-P — March 2014
Bulletin 1606 Switched Mode Power Supplies
Switching Frequencies
The power supply has two converters with two different switching frequencies included.
Switching frequency 1
70kHz to 130kHz
PFC converter, input voltage and output power dependent
Switching frequency 2
80kHz to 140kHz
Main converter, output power dependent
15. Environment
Operational temperature
*)
-25°C to +70°C (-13°F to 158°F)
reduce output power according Fig. 15-1
Storage temperature
-40 to +85°C (-40°F to 185°F)
for storage and transportation
Output de-rating
6.4W/°C
12W/°C
45°C to 60°C (113°F to 140°F)
60°C to 70°C (140°F to 158°F)
Humidity
**)
5 to 95% r.h.
IEC 60068-2-30
Vibration sinusoidal
2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g
***)
2 hours / axis
IEC 60068-2-6
Shock
30g 6ms, 20g 11ms
***)
3 bumps / direction, 18 bumps in total
IEC 60068-2-27
Altitude
0 to 2000m (0 to 6 560ft)
without any restrictions
2000 to 6000m (6 560 to 20 000ft)
reduce output power or ambient temperature,
see Fig. 15-2
IEC 62103, EN 50178, overvoltage category II
Altitude de-rating
30W/1000m or 5°C/1000m
> 2000m (6500ft), see Fig. 15-2
Over-voltage category
III
IEC 62103, EN 50178, altitudes up to 2000m
II
altitudes from 2000m to 6000m
Degree of pollution
2
IEC 62103, EN 50178, not conductive
LABS compatibility
The unit does not release any silicone or other LABS-critical substances and is suitable for
use in paint shops.
Audible noise
At load currents below 1A some audible noise will be emitted from the power supply
*) Operational temperature is the same as the ambient temperature and is defined as the air temperature 2cm below the unit.
**) Do not energize in the presence of condensation.
***) Higher levels allowed when using the 1606-XLC wall mounting bracket.
Fig. 15-1
Output current vs. ambient temp.
Fig. 15-2
Output current vs. altitude
Allowed Output Current at 48V
0
-25
0
20
40
70°C
2A
4A
6A
8A
10A
12A
60
B
A
Ambient Temperature
A...100 to 264Vac, continuous
B... 85Vac, continuous
C... Short term
C
0
0
2000m
4000m
6000m
2A
4A
6A
8A
10A
12A
B
A
C
A... Tamb < 60°C
B... Tamb < 50°C
C... Tamb < 40°C
D... Short term
D
Allowable Output Current at 48V
Altitude
See section 3 for derating requirements for input voltages between 85Vac and 100Vac.
Summary of Contents for 1606-XLC
Page 25: ......