A variety of cable types are acceptable for
variable speed controller installations. For many
installations, unshielded cable is adequate,
provided it can be separated from sensitive
circuits. As an approximate guide, allow a
spacing of 1 meter (3.3 feet) for every 10 meters
(33 feet) of unshielded length. If you cannot
separate motor cables from sensitive circuits, or if
you must run motor cables from multiple
controllers (more than three) in a common
conduit or cable trays, shielded motor cable is
recommended to reduce system noise.
Motor cables should be four-conductor with the
ground lead and shield (if using shielded cable)
connected to the controller ground terminal and
the motor frame ground terminal.
Installations with long motor cables may require
the addition of output reactors to reduce voltage
reflections at the motor, and reduce cable
charging current. Capacitive charging of long
motor cables may draw current in excess of the
controller rating. The controller should be
installed as close to the motor as possible.
Important: Both Reflected Wave and Capacitive
Current Considerations need to be taken into
account when determining motor cable lengths.
Refer to Table 2.D and Table 2.E .
# "
"
380–460 V
Ratings
!
Ratings
!
1000 Vp-p
40
12
40
12
40
12
40
12
210
64
210
64
2.2 kW
(3 HP)
1200 Vp-p
60
18
60
18
180
55
180
55
260
79
260
79
(3 HP)
1600 Vp-p
500
152
500
152
500
152
500
152
500
152
500
152
1000 Vp-p
40
12
40
12
45
14
50
15
250
76
250
76
1.5kW
(2 HP)
1200 Vp-p
60
18
60
18
300
91
200
61
340
104
340
104
(2 HP)
1600 Vp-p
500
152
500
152
500
152
500
152
500
152
500
152
1000 Vp-p
55
17
40
12
55
17
40
12
325
99
325
99
0.75 kW
(1 HP)
1200 Vp-p
125
43
60
18
180
55
120
37
500
152
325
99
(1 HP)
1600 Vp-p
500
152
500
152
500
152
500
152
500
152
500
152
1000 Vp-p
45
14
40
12
45
14
40
12
300
91
300
91
0.55 kW
(0.75 HP)
1200 Vp-p
125
38
60
18
75
23
75
23
500
152
500
152
(0.75 HP)
1600 Vp-p
500
152
500
152
500
152
500
152
500
152
500
152
1000 Vp-p
45
14
40
12
45
14
40
12
300
91
300
91
0.37 kW
(0.5 HP)
1200 Vp-p
125
38
50
15
75
23
75
23
500
152
500
152
(0.5 HP)
1600 Vp-p
500
152
500
152
500
152
500
152
500
152
500
152
$& )( & ""% &! $#' % &! + !$ $& % %
*' ",&!," (!& ! & ! &$!$ % ' &! & ' ! ! & %!&)$
&( ( %& % ! ! &% '" &! &
!$ "&( '$$ & ! %$&! %
Summary of Contents for 160 SSC
Page 9: ...ii This Page Intentionally Blank...
Page 11: ...ii This Page Intentionally Blank...
Page 23: ...2 10...
Page 33: ...5 6 Program Group P Parameter Description 41 0 4 2 42 43 2 1 44 1 1 3 3 45 0 1 3 3 2 0 1...
Page 41: ...6 2...
Page 54: ...Index I 1 4 1 4 1 1 0 3 1 3 3 1 1 1 1 0 0 3 3 3 0 4 3 1 3 1 2 3 1 3 1 3 0...
Page 55: ...Index I 2 0 0 0 0 0 0 0 0 0...
Page 57: ......
Page 58: ......