Chapter 2 -
,01 ** 1(-,(/(,&
2–3
Power Wiring For Preset Speed and
Analog Signal Follower Models
Table 2.A Power Terminal Block Specifications
Terminal
Block
Screw
Size
Max/Min Wire
Size mm
2
(AWG)
Max/Min Torque
Nm. (lb.in.)
TB1
À
M4
4-0.75 (12-18)
1.81-1.35 (16-12)
TB2
À
M4
4-0.75 (12-18)
1.81-1.35 (16-12)
À
'$ 2**$1(, (0 3(1' 3(/$0 (,01 **$# -, .-3$/
1$/+(, * !*-")0
Recommended Line Side Protection
The Bulletin 160 Smart Speed Controller has
been UL tested and approved for use with up to a
30 Amp protective device (fuse, circuit breaker,
manual motor starter) installed on the line side of
the drive for the purposes of branch circuit
protection. The ratings in Tables 2.B and 2.C are
the minimum recommended values for use with
each drive rating. The model numbers of the
devices listed in these tables are provided to serve
as a guide. Other devices which meet the
requirements of UL508C and UL489 with similar
trip characteristics may be used. For applications
with greater than five controllers per branch
circuit, consult factory for group fusing
recommendations.
Input Power Conditioning
The controller is suitable for direct connection to
AC power lines within the rated voltage of the
controller (see Appendix A). Listed below are
certain power line conditions which may cause
component damage or reduction in product life. If
any of the conditions exist as described in the
table below, install “one” of the devices listed
under the heading “Corrective Action” on the line
side of the controller. Note: Only one device per
branch circuit is required. It should be mounted
closest to the branch and sized to handle the total
current of the branch circuit.
Power Line Condition
Corrective Action
Low Line Impedance (less than
1% line reactance)
Line Reactor (See A-4) or
Isolation Transformer
Line has power factor correction
capacitors
Line Reactor (See A-4) or
Isolation Transformer
Line has frequent power
interruptions
Line Reactor (See A-4) or
I
solation Transformer
Line has high frequency
(>10 Hz) noise spikes in excess of
900V (Induction heaters, RF
equipment, choppers)
MOV option (See A-4) or
Line Reactor (See A-4) or
Isolation Transformer
Line has intermittent noise spikes
in excess of 2000V (lightening)
MOV option (See A-4) or
Line Reactor (See A-4) or
Isolation Transformer
Table 2.B Recommended Line Side Protective Devices for 200-240V rated units
3
∅
Rating
kW (HP)
1
∅
Rating
kW (HP)
Fuse
R ti
Fuse Types
Ç
Other Protective Devices
∅
g
kW (HP)
∅
g
kW (HP)
Rating
Class CC
Class J
Rating
Type
.37 (1/2)
N/A
6
16
.37 (1/2)
.55 (3/4)
N/A
.37 (1/2)
6
6
KLDR/CCMR
Á
JDT
Á
16
16
140-MN-****
Ä
.55 (3/4)
.75 (1)
.37 (1/2)
.55 (3/4)
6
10
KLDR/CCMR
ATMR
Â
JDT
AJT
Â
16
16
140 MN
1492-CB3-H***
Å
.75 (1)
1.5 (2)
.55 (3/4)
.75 (1)
10
15 (16)
ATMR
FNQR
Ã
AJT
LPJ
Ã
16
16
1492 CB3 H
HFD ***L
Æ
1.5 (2)
2.2 (3)
.75 (1)
1.5 (2)
15 (16)
25
FNQR
LPJ
16
20
HFD L
Table 2.C Recommended Line Side Protective Devices for 380-460V rated units
3
∅
Rating
kW (HP)
1
∅
Rating
kW (HP)
Fuse
R ti
Fuse Types
Ç
Other Protective Devices
∅
g
kW (HP)
∅
g
kW (HP)
Rating
Class CC
Class J
Rating
Type
.37 (1/2)
N/A
3 (4)
À
16
.37 (1/2)
.55 (3/4)
N/A
N/A
3 (4)
À
3 (4)
À
KLDR/CCMR
Á
Â
JDT
Á
Â
16
16
140-MN-****
Ä
Å
.55 (3/4)
.75 (1)
N/A
N/A
3 (4)
6
À
KLDR/CCMR
ATDR/ATQR
Â
Ã
JDT
AJT
Â
Ã
16
16
140 MN
1492-CB3-H***
Å
Æ
.75 (1)
1.5 (2)
N/A
N/A
6
10
ATDR/ATQR
FNQR
Ã
AJT
LPJ
Ã
16
16
1492 CB3 H
HFD ***L
Æ
1.5 (2)
2.2 (3)
N/A
N/A
10
15 (16)
FNQR
LPJ
16
20
HFD L
À
201 !$ #2 * $*$+$,1
1(+$ #$* 4
Á
(11*$%20$
Â
-2*# ' 3+21
Ã
200+ ,
Ä
**$,/ #*$4 2**$1(,
+ ,2 * +-1-/
01 /1$/
Å
**$,/ #*$4
2**$1(, "(/"2(1
!/$ )$/
Æ
$01(,&'-20$ 14.$
"(/"2(1 !/$ )$/
Ç
-,1/-**$/ (0 *0-
"-+. 1(!*$ 3(1'
,#
%20$ 14.$0
20$ / 1(,&0 (, #$,-1$
2/-.$ , 0(5$
Summary of Contents for 160 SSC
Page 9: ...ii This Page Intentionally Blank...
Page 11: ...ii This Page Intentionally Blank...
Page 23: ...2 10...
Page 33: ...5 6 Program Group P Parameter Description 41 0 4 2 42 43 2 1 44 1 1 3 3 45 0 1 3 3 2 0 1...
Page 41: ...6 2...
Page 54: ...Index I 1 4 1 4 1 1 0 3 1 3 3 1 1 1 1 0 0 3 3 3 0 4 3 1 3 1 2 3 1 3 1 3 0...
Page 55: ...Index I 2 0 0 0 0 0 0 0 0 0...
Page 57: ......
Page 58: ......