All Seasons Hire Red Star Instruction Manual Download Page 5

GB

2

TROUBLE

Heater does not start

Heater starts, flame ignites 
but then heater locks out

Heater starts, flame does 
not ignite and then heater 
locks out

Heater starts, but combu-
stion is not good 

Heater stops due to safety 
thermostat 

CAUSE

No power 

Faulty cable/connections

Burnt fuse

Room thermostat set too low 

Thermostat socket cap not inserted

The safety thermostat has been activated 

Dirty or faulty flame sensor 

Faulty burner control unit
 

Clogged nozzle

Flame sensor receives an external light 
signal during ignition sequence

Faulty burner control unit

No fuel

Ignition fault, dirty or incorrectly 
spaced electrodes 

Dirty or blocked nozzle

Clogged filters

Leakes in fuel circuit

Oil pump provides low pressure

Insufficient combustion air

Insufficient ventilation air

The appliance has overheated

Faulty safety thermostat

SOLUTION

Check main distribution board and power supply line 

Check/have cable replaced by a 
qualified electrician

Check and replace if required

Set room thermostat on a higher temperature

Insert cap into the thermostat socket

Reset the safety thermostat

Clean or replace

Contact service personnel

Clean or replace

Check for external lights (sun, lamps, etc.)  

Contact service personnel

Fill tank

Clean electrodes, contact service personnel if 
required

Clean or replace

Clean or replace

Check and eventually replace

Contact service personnel

Pulire la fotocellula e, se questo non basta, 
rivolgersi a personale specializzato 

Wrong air lock setting 

Contact service personnel

Contact service personnel

6. TROUBLESHOOTING

Never disconnect the supply plug to stop the heater 

while in operation

The big amount of heat produced could damage the 

components or activate the safety thermostat and 

therefore make the unit not function 

5. MAINTENANCE

• Before carrying out any maintenance operation, disconnect 

the power plug.

• Maintenance must be carried out by qualified personnel (see 

also par. 7)

• The appliance must be thoroughly cleaned once a year to 

ensure good combustion and long life.

• Clean periodically
  the oil spraying nozzle and its filter;
  the oil pump filter
  the main fuel filter cartridge
  the ignition electrodes
  the fan blades
  the inside of the appliance, using compressed air
  the flame sensor with a mild detergent 
• Periodically check cables and electrical connections 
• Check the oil filter and replace if necessary.

WARNING!

Heaters equipped with heated nozzle do not start im-

mediately or may stop for some seconds after start. 

This is normal and should not be considered a faulty 

condition.

4.2. Reset after lockout and Reset of safety thermostat

• The heater is equipped with a Reset pushbutton. When the 

heater locks out, the red lamp on the pushbutton (fig. 1 n°2) 
lights up. In this case push the Reset button (see also the par. 
“Troubleshooting”) to restart the heater.   

• The heater is also equipped with a manual reset safety ther-

mostat fixed to the combustion chamber, that can be rea-
ched through the inspection cover. To reset the thermostat:  
unplug the heater, open the inspection cover and push the 
reset  button on the thermostat body. 

4.3. Shut down.

• Set switch to “OFF” to shut the flame off. The fan will go on 

rotating for about 1’45’’ to cool the heater down. The fan 
motor will automatically stop at the end of the aftercooling 
time, then the unit can be disconnected from mains.

Summary of Contents for Red Star

Page 1: ...Instruction Manual Red Star Mobile Direct Fired Diesel Heater Hanging Indirect Fired Diesel Heater Mobile Indirect Fired Diesel Heater...

Page 2: ...rein has been prepared by qualified experts While we believe the information is accurate and complete we make no warranty or representation for any particular purposes The information is offered in go...

Page 3: ......

Page 4: ...DANGER OF BURNS THE HEATER IS INTENDED FOR PROFESSIONAL USE ONLY 2 APPLIANCE DESCRIPTION Mobile space heater with closed combustion chamber and gas exhaust duct indirect red models open combustion cha...

Page 5: ...r disconnect the supply plug to stop the heater while in operation The big amount of heat produced could damage the components or activate the safety thermostat and therefore make the unit not functio...

Page 6: ...assergesch tztem Stecker verwenden Die Abgasrohre nicht ber hren Verbrennungsgefahr Die Ger te d rfen nur zu gewerblichen Zwecken eingesetzt werden 2 GER TEKURZBESCHREIBUNG Ortver nderlicher lbefeuert...

Page 7: ...at bet tigen so dass das Ger t au er Betrieb gesetzt wird 5 WARTUNG Wartungsarbeiten nur bei herausgezogenem Netzstecker vor nehmen Die Wartung muss von Fachleuten durchgef hrt werden siehe auch 7 Ein...

Page 8: ...ar du Personnel agr Il faut utiliser uniquement un c ble du type H07RN F avec prise prot g e contre les projections d eau Ne pas toucher le conduit de sortie des gaz de combustion risque de br lures L...

Page 9: ...teur continue tourner pendant 1 45 environ pour refroidir la chambre et pass ce temps l appareil s arr te automatiqment Ne jamais arr ter le g n rateur en d branchant la prise d alimentation lectrique...

Page 10: ...Pericolo di scot tature L apparecchio deve essere installato esclusivamente per uso indu striale 2 DESCRIZIONE DELL APPARECCHIO Generatore di aria calda mobile a gasolio con camera di combustione chiu...

Page 11: ...e delle connessioni elettriche Controllare periodicamente le condizioni del filtro gasolio e se necessario sostituirlo ATTENZIONE Sui modelli con ugello riscaldato il fatto che il generatore non si av...

Page 12: ...gases de descarga i Peligro de quemaduras El aparato se debe instalar exclusivamente para un uso industrial 2 DESCRIPCI N DEL APARATO Generador m vil de aire caliente a gas leo con c mara de combusti...

Page 13: ...entilador continuar dando vuelta por aproximadamente 1 e 45 para enfriar el generador el aparato se apaga solo cuando acaba este tiempo programado sobre la ficha electr nica Despu s se puede desconect...

Page 14: ...RU 11 0 1 1 3 0 033 1 3 17 4 4 1 220 1 1 220 50 1 4 1 H07RN 2 3 3 1 50 3 500 3 25 600 3 30 800 3 40 1500 3 75 80 3 2 5 0 8 2 0 60 0 60 1 50 3 00 3 2 1 2 3 4 Fig 1...

Page 15: ...RESET 4 4 OFF 3 5 7 0 1 3 4 1 3 ON 4 2 ON 1 2 3 4 3 RESET 1 2 1 2 RU 12 6 IT 09 00886 12 2 042 91 3 4 2 2 6 4 12 1 004 91 12 1 003 83 2 3 12 5...

Page 16: ...eo Ugello gasolio 0 65 60 H 1 00 60 H 1 25 60 S 1 50 80 W 2 25 80 W Efficiency Rendement Wirkungsgrad Rendimiento Rendimento 87 1 87 1 100 88 5 100 Noise Level at 2m dB A Niveau sonore 2m dB A Ger usc...

Page 17: ...Altezza mm 790 790 750 938 898 Flue Diameter mm Diam tre chemin e mm Abgasrohrdurchmesser mm Di metro de la chimenea mm Diametro del camino mm 150 150 150 Tank Capacity l Capacit du r servoir l Tankin...

Page 18: ...mostat d ambiance optionnel FR Filtre r chauffeur optionnel EV Magnetventil TR Z ndtransformator M Motor SL Kontrolllampe TS Sicherheitsthermostat FS Sicherung FC Photowiderstand PL RESET Knopf IN Sch...

Page 19: ...e r chauffeur optionnel UR Gicleur r chauffeur optionnel EV Magnetventil TR Z ndtransformator M Motor SL Kontrolllampe TS Sicherheitsthermostat FS Sicherung FC Photowiderstand PL RESET Knopf IN Schalt...

Page 20: ...E MONTAGE PIED MONTAGGIO PIE DE During the tting of the single parts please follow the numerical order Bei der Montage der einzelnen Teile mu die Zahlenfolge beachtet werden Dans le montage des compos...

Reviews: