TECHNICAL DATA &
Page
5
of
7
ANC 303
CHARACTERISTIC CURVES
ALUMINIUM INDUSTRIES LIMITED
Relays Division
RELAY SETTINGS
ANC 214
Settings
Particulars
1.
General config.
1.1
Trip Ckt Supervision (EN/DIS)
1.2
Line CT Primary
5 to 1600A in steps of 5A
1.3
Line CT Secondary
1 to 5A in steps of 1A
1.4
Unbalance CT Primary
1 to 5A in steps of 1A
1.5
Unbalance CT Secondary
1 to 5A in steps of 1A
1.6
Switching CT Primary
5 to 1600A in steps of 5A
1.7
Switching CT Secondary
1 to 5A in steps of 1A
1.8
Trip counter Reset
Reset/Discard
1.9
Post fault cycle
0 to 5 in steps of 1
1.10
Relay ID
1 to 255 in steps of 1
1.11
Baud Rate
4800-57600 in steps of 200
1.12
Set Date Time
(Yes/No)
DD/MM/YYHH:MM:SS
1.13
Trip Relay Test
2.
IDMT OC Protection
2.1
IDMT Current
5 to 200% in steps of 1%
2.2
IDMT TMS
0.01 to 1 sec in steps of 0.01 sec
3.
Current Unbalance
3.1
Current Unbalance
2.5 to 100% in steps of 0.5%
3.2
Unbalance time
0 to 1000ms in steps of 1 ms
4.
Dynamic capacitor switching element
4.1
Switching in current
2 to 40% in steps of 0.1%
4.2
Switching in ON delay
1 to 100sec in steps of 1 sec
4.3
Switching out current
2 to 40% in steps of 0.1%
4.4
Switching out ON delay
60 to 1800sec in steps of 30 sec
5.
Time Delay Relay
5.1
TDR relay
0 to 600 sec in steps of 20 sec
6.
Local Breaker Backup
6.1
LBB (EN/DIS)
6.3
LBB Time
0 to 5000ms in steps of 1 ms
Summary of Contents for AN Series
Page 3: ...Page 1 of 7 ANC 303 ALUMINIUM INDUSTRIES LIMITED Relays Division SAFETY REQUIREMENTS ...
Page 10: ...Page 1 of 4 ANC 303 ALUMINIUM INDUSTRIES LIMITED Relays Division INTRODUCTION ...
Page 21: ...Page 1 of 16 ANC 303 THE ALUMINIUM INDUSTRIES LIMITED Relays Division USER GUIDE ...
Page 44: ...Page 1 of 4 ANC 303 ALUMINIUM INDUSTRIES LIMITED Relays Division TEST REPORT ...
Page 48: ...Page 1 of 2 ANC 303 ALUMINIUM INDUSTRIES LIMITED Relays Division TROUBLESHOOTING ...