81
HD-TVI 30x Zoom PTZ IR Outdoor Camera User Manual
APPENDIX C: 24 VAC WIRE GAUGE AND TRANSMISSION DISTANCE
APPENDIX C
24 Vac Wire Gauge and Transmission Distance
The following table shows the recommended maximum distance adopted for the different wire sizes when the 24 Vac voltage loss is
less than 10%. For the AC driven device, the maximum voltage loss rate allowable is 10%. For example, for a device with the rating
power of 80 VA which is installed 35 feet (10 m) from the transformer, the minimum wire gauge required is 0.8000 mm.
Table 5. Table of wire gauge standards
Distance: ft (m)
Wire Gauge (mm)
Power (VA)
0.8000
1.000
1.250
2.000
10
283 (86)
451 (137)
716 (218)
1811 (551)
20
141 (42)
225 (68)
358 (109)
905 (275)
30
94 (28)
150 (45)
238 (72)
603 (183)
40
70 (21)
112 (34)
179 (54)
452 (137)
50
56 (17)
90 (27)
143 (43)
362 (110)
60
47 (14)
75 (22)
119 (36)
301 (91)
70
40 (12)
64 (19)
102 (31)
258 (78)
80
35 (10)
56 (17)
89 (27)
226 (68)
90
31 (9)
50 (15)
79 (24)
201 (61)
100
28 (8)
45 (13)
71 (21)
181 (55)
110
25 (7)
41 (12)
65 (19)
164 (49)
120
23 (7)
37 (11)
59 (17)
150 (45)
130
21 (6)
34 (10)
55 (16)
139 (42)
140
20 (6)
32 (9)
51 (15)
129 (39)
150
18 (5)
30 (9)
47 (14)
120 (36)
160
17 (5)
28 (8)
44 (13)
113 (34)
170
16 (4)
26 (7)
42 (12)
106 (32)
180
15 (4)
25 (7)
39 (11)
100 (30)
190
14 (4)
23 (7)
37 (11)
95 (28)
200
14 (4)
22 (6)
35 (10)
90 (27)
Summary of Contents for ALI-PTZ30XR