24
Er41
The minimum primary air flow in
the Check Up Phase has not been
achieved
The presence of some
obstacle or large
impurities in the primary
air inlet pipe
Wait for the boiler to
turn down and then
press the P2 key for
more than 3
seconds
Check and clean the
primary air inlet pipe
Check how dirty the
flue pipe and
chimney are and
their draught
Flue pipe obstructed
The door not closed well in
the Ignition Phase
Check that the door
of the chamber
closes well
Contact the
maintenance staff
Er42
The primary air flow is greater than
the maximum allowed value
Too large inlet air
Wait for the boiler to
turn down and then
press the P2 key for
more than 3
seconds
Check the primary
air inlet pipe
Check how dirty the
flue pipe and
chimney are and
their draught
Contact the
maintenance staff
NOTE: If the recommended solution to the problem does not remove the direct cause of the alarm, YOU MUST CONTACT “ALFA
PLAM” CALL CENTRE or the nearest authorized maintenance service centre.
INFORMATION ON THE DISPOSAL AND DISASSEMBLY OF THE BOILER
The owner of the boiler is responsible for its disposal and disassembly (as a waste material).
The owner must comply with the applicable regulations of the country in which the boiler is being disposed of for the sake
of safety and environmental protection. The disposal of the boiler can also be entrusted to a third person who is licensed for
such activities.
INDICATION: In any case, you must comply with the laws of the country in which the pellet boiler is installed.
WARNING: All disassembled parts intended for destruction must be properly removed:
- Remove all electrical parts,
- Separate the battery from the electronic system,
-Dispose of the battery separated from the electronic system in provided containers in accordance with the norms,
- Separate the base of the boiler and take care of it as scrap.
WARNING: If you dispose of the boiler in the environment, it may become a serious danger to people and animals.
The owner of the boiler is always responsible for the resulting damage.
When the boiler is disposed of, it is necessary to take care of the CE mark, Operation Manual and all other installation related
documents.
TECHNICAL CHARACTERISTICS OF COMMO COMPACT 32 PELLET BOILER
Characteristic name
Value
Reduced
(minimum)
Nominal (maximum)
*Boiler power (kW)
9.8
31.7
*Utilization rate (%)
93.6
90.34
Consumption of pellets per hour kg / h
2.13
7.14
CO emissions (at 10% O2) (%)
0.008
0.032
Flue pipe connection (mm)
Ø100
Boiler Class
Class 5
Weight (kg)
360 - 380
Fuel
pellet
Pellet tank (kg)
~ 70
Voltage (V)
220-230
Frequency (Hz)
50
Electricity consumption while boiler operates at nominal power (W)
53
Electricity consumption while boiler operates at reduced power (W)
37
Electricity consumption during boiler Ignition Phase (W)
310
Electricity consumption during boiler Standby Phase (W)
3
Necessary draught at the nominal boiler power (mbar)
0.103