18 

 

 

The desired combustion power is selected by pressing the P4 and P6 keys. Press the P3 key to save the new parameter set 

value. To cancel all modifications and return to the old values, press the P1 key. 
 
10.3.1.2 Combustion Recipe 

Combustion Recipe Menu. If only one recipe is set at the factory, this menu is not available. 

 
10.3.1.3 Auger Calibration 

This menu is used for changing the auger feeding rate. The system has 10 calibration steps (from -5 to +5, the factory 

default is 0). The calibration effect is valid in the Run Mode and in the Modulation. For each step, the value is increased or 
decreased by 5%. 

Example: Calibration value = -2; (-2 * 5% = - 10%) This means that the calibrated velocity values of the auger will be 

reduced by 10% compared to the factory values. 

Factory set values  

C03=600  

C04=900  

C05=1200  

C06=1600  

C07=2000  

C11=600  

Calibrated values  

C03=540  

C04=810  

C05=1080  

C06=1440  

C07=1800  

C11=540  

 
10.3.1.4. Combustion Fan Calibration 

This menu is used for changing the number of revolutions of the combustion fan. The system has 10 calibration steps 

(from -5 to +5, the factory default is 0). The calibration effect is valid in the Run Mode and in the Modulation. For each step, the 
value is increased or decreased by 5%. 

Example: Calibration value = + 3; (+ 3 * 5% = + 15%). This means that the calibrated combustion fan speed values will be 

increased by 15% compared to the factory values. 

Factory set values 

 U03=1000  

U04=1200  

U05=1400  

U06=1600  

U07=1800  

U11=900  

Calibrated values      

 U03=1150  

U04=1380  

U05=1610  

U06=1840  

U07=2070  

U11=1030  

Note: The calibration of the auger and flue gas motor should not be carried out without prior consultation with the 

authorized maintenance staff or representative of the manufacturer. 

 

 

Heating Management Menu  

This is a menu for setting the parameters that determine the heating performance of the boiler . It contains several 

submenus. By pressing the P3 key you enter the menu and you can see the following submenus:  

 

 

10.3.2.1. Boiler Thermostat 

 This menu allows you to adjust the so-called set water temperature in the boiler. The temperature range of the water in the 

boiler can be adjusted from 30 ° C to 80 ° C. By adjusting the set value of the water temperature in the boiler, the user sets the 
operating condition of the boiler, i.e. the boiler will operate at the set power until it reaches the set water temperature in the 
boiler. When the set value of the water temperature in the boiler is reached, the boiler goes into the state of modulation i.e. it 
continues to operate at minimum power. 

We do not recommend setting the water temperature below 57ºC due to possible condensation of the boiler, nor over 75ºC

 
10.3.2.2. Buffer Thermostat  

This menu allows the buffer temperature to be modified. This menu is only active if the buffer is installed. 

 
10.3.2.3. Room thermostat  

In this menu, the ambient probe temperature is modified. This menu is only visible if the ambient probe option or room 

thermostat has been activated. 
 
10.3.2.4. Summer – Winter 

In this menu, the functionality of the boiler is changed depending on the season. The display shows one of two symbols:

 
10.3.2.5 Heating Power 

 

 

 

 

 

 

Currently set power: Power 1 

 

 

  

 

 

 

 

 

 

 

Summary of Contents for COMMO COMPACT 32

Page 1: ...COMPACT 32 Installation Operation and Maintenance Manual This product meets the requirements of the Ecodesign Directive in terms of efficiency and air pollution level in order to contribute to the re...

Page 2: ...ACCUMULATING BOILER ETC 18 LITRE EXPANSION TANK ENOUGH FOR 37 5 KW HEATING POWER AUTOMATIC AIR VENT VALVE SET ON THE HOT WATER OUTLET FROM THE BOILER SAFETY VALVE INSTALLED ON THE HOT WATER OUTLET FRO...

Page 3: ...IONAL MAINTENANCE 10 CHARACTERISTIC BUILT IN ELEMENTS 11 CIRCULATION PUMP 11 EXPANSION TANK 11 FILL AND DRAIN COCK 11 ELECTRONIC SYSTEM 11 NON RETURN VALVE AUTOMATIC AIR VENT VALVE SAFETY VALVE AND WA...

Page 4: ...Pellet boiler hydraulic installation diagram radiator and floor heating 27 Pellet boiler hydraulic installation diagram accumulation tank 28...

Page 5: ...approach the boiler while in operation with the intention of playing This appliance can be used by children aged 8 and older and persons with reduced physical sensory or mental abilities if they are...

Page 6: ...this document The installer is to check whether the air supply pipes correspond to the type of the installed boiler The electrical connections must not be executed with the use of temporary and or uns...

Page 7: ...east 100 cm2 or bigger The boiler operates at 220 230 V 50 Hz Ensure that the electrical cables do not go under the boiler that they are away from hot surfaces and that they cannot come in contact wit...

Page 8: ...the qualified chimney sweep Flue gases can be discharged directly into the chimney only if it has a cap for the purposes of inspection and cleaning and if its cross section is up to 20 x 20 cm i e if...

Page 9: ...for a longer distance In this case the length is up to 8m INSULATION AND DIAMETER OF THE OPENINGS ON THE ROOF Once the position of the boiler has been determined it is necessary to make a hole i e an...

Page 10: ...Grounding is prescribed by the law Under no circumstances may the electrical cable be exposed to a temperature above 80 C The power cable is part of the equipment that is supplied with the boiler It i...

Page 11: ...uality and do not use any other types of fuel Inform all users on possible risks and hazards and show them how to handle the pellet boiler If the boiler is placed on a wooden floor it should be insula...

Page 12: ...ing value min 16 9 MJ kg or 4 7 kWh kg ash content below 0 7 DO NOT use the boiler for burning garbage Always take care of maximum safety GUIDELINES FOR SAFE IGNITING AND CLEANING THE BOILER NEVER use...

Page 13: ...l forward and by lowering it Figure 12b Take the upper ashtray out and pour the ashes into the garbage bin Then clean the ashtray and the space around the ashtray in the boiler with the vacuum cleaner...

Page 14: ...er clarifications The manufacturer does not have direct supervision over the work of the installer and cannot guarantee for the performed works or maintenance works In no case does the manufacturer as...

Page 15: ...e careful when connecting to a heating installation so that it does not rotate When the pump does not operate for a long period of time there is a risk that the pump shaft jams and cannot start at the...

Page 16: ...to the valve you must take the right side off when facing the boiler Valve safety cap should be loose not too tight so that the air could freely leave 7 4 5 3 SAFETY VALVE The safety valve is with R1...

Page 17: ...firemen In order to preserve safety and proper functioning of the pellet boiler do not use chopped wood Do not use the boiler for burning garbage THE PELLET QUALITY IS VERY IMPORTANT The pellet quali...

Page 18: ...system BOILER CONTROL SYSTEM The boiler has an advanced control system that allows safe efficient and reliable operation control and maximum functional utilization of the boiler It is characterized b...

Page 19: ...outlet has been activated L4 Additional motor Led light is on Additional motor has been activated L5 Aux 2 outlet Led light is on Aux 2 outlet has been activated L6 Aux 3 outlet Led light is on Aux 3...

Page 20: ...ode Link Error This message informs you that there is no communication between the LCD display and the controller in the boiler Standby Man This message appears if the system is in Standby Mode after...

Page 21: ...eters Chrono Menu for selecting modality of the Chrono Program and boiler turn on off time Manual Load Menu for manual loading of the auger It is only feasible when the system is in the OFF state Time...

Page 22: ...50 U04 1380 U05 1610 U06 1840 U07 2070 U11 1030 Note The calibration of the auger and flue gas motor should not be carried out without prior consultation with the authorized maintenance staff or repre...

Page 23: ...hrono Program By entering the Chrono Menu you see two submenus Modality and Programming Press the P4 and P6 keys to choose one of the submenus and then enter it by pressing the P3 key When you enter t...

Page 24: ...pressing the P4 and P6 keys the hours minutes years months and days are set By pressing the P3 key you enter the change mode and by pressing the P4 and P6 keys you change the value If you press the P...

Page 25: ...lighter Ignition Preload At this stage pellets are preloaded i e the auger loads a certain quantity of pellets that is necessary for ignition At this stage the lighter auger and flue gas motor are act...

Page 26: ...The minimum duration of this phase is 300 seconds and the flue gas temperature needs to be less than 70 C in order to extinguish the furnace completely OFF In this phase the boiler is extinguished flu...

Page 27: ...he furnace to extinguish and then press the P2 key for more than 3 seconds Check the condition and quality of the used pellet The appropriate flue gas temperature has not been reached during the Ignit...

Page 28: ...an also be entrusted to a third person who is licensed for such activities INDICATION In any case you must comply with the laws of the country in which the pellet boiler is installed WARNING All disas...

Page 29: ...r mg m3 26 2 Flue gas mass at nominal power kg s 0 0175 Flue gas mass at reduced power kg s 0 0072 Maximum operating water pressure bar 2 Maximum operating water temperature C 80 Boiler capacity l 68...

Page 30: ...COMMO CONTACT 32 BOILER HYDRAULIC INSTALLATIONS DIAGRAM OF COMMO CONTACT 32 PELLET BOILER In order to reduce the risk of condensation install a three way mixing valve with a pipe thermostat when insta...

Page 31: ...ydraulic installation diagram radiator and floor heating Legenda 1 Pellet boiler 2 Three way mixing valve with pipe thermostat Legenda 1 Pellet boiler 2 Hydraulic separator 3 Circulation pump 4 Three...

Page 32: ...aulic installation diagram accumulation tank Legend 1 Pellet boiler 2 Air vent 3 Safety valve 3 bar 4 Air vent 5 Circulation pump 6 Three way mixing valve with pipe thermostat 7 Accumulation tank BUFF...

Reviews: