LED ON: No pellets in hopper

 

 

L10

 

LED ON: Summer mode selected

 

 

L11

 

LED ON: Winter mode selected

 

 

 

L12

 

LED ON: Pellet safety valveorPellet feeder motororCleaning motor is active (only for V2 out)

 

 

L13

 

LED ON: Request for running water (closed contact). 
Only for hydraulic systemswhich have available use of 

Flow Switch

.

 

 

 

DISP LAY 

Below are depicted three types of displays, respectively: 

 

• 

Variables displayed on the main screen: 

• 

Upper display: time, operation mode, error, menu, sub-menu, values 

• 

Lower left display: power, parameter code 

• 

Lower right display: main temperature, parameter code 

• 

Indicated operation status: 

• 

Check Up (CHEc) 

• 

Ignition (On 1, On 2, On 3, On 4) 

• 

Stabilization (On 5) 

• 

Modulation (Mod) 

• 

Stand By (StBY) 

• 

Normal 

• 

Safety (SAF/Erxx) 

• 

Extinguishing (OFF) 

• 

RecoverIgnition (rEc) 

• 

Block (Alt/Erxx) 

• 

Errors (Alarms) 

 

DISPLAY 

DESCRIPTION 

Er01 

Safety thermostat activated 

Er02 

Safety manometer activated 

Er03 

Extinguishing due to low temperature of flue gases 

Er04 

Extinguishing due to high water temperature in the boiler 

Er05 

Extinguishing due to high temperature of flue gases 

Er07 

Encoder error. No signal 

Er08 

Encoder error. Unable to adjust number of revolutions 

Er09 

Low water pressure 

Er10 

High water pressure 

Er11 

Error due to problems with the internal clock 

Er12 

Extinguishing due to ignition failure 

Er15 

Power outage longer than 50 minutes 

Er17 

Airflow regulator error 

Er39 

Airflow regulator error 

Er41 

Minimum airflow in CHECK UP phase not reached 

Er42 

Maximum airflow exceeded 

 

Other messages 

Display 

Description 

Sond 

Display status of temperature probes. The message is displayed during the check up phaseand indicates that 
the  temperaturewhich  is  read  on  one  or  moreprobesequal  to  the  minimum  value  (0°C)  or  maximum 
value(depending on the probe in question). Check that probes are not open (0°C) ora short circuit occurred 
(reading the maximum value on temperature scale). 

Hi 

Water temperature in the boiler exceeds 99°C. 

FLu 

The  message  is  displayed  during  normal  phaseand  indicatesthere  is  a  request  for  running  water. 

Only  for 

hydraulic systems which have available use of 

Flow Switch

.

 

OFF dEL 

The message that appears if the system is not switched off  manually during ignition (after Preload): the 
system stops only when it reaches the speed. 

 
 
 

 

MENU 

 

Summary of Contents for CFH XILA

Page 1: ...METALNA INDUSTRIJA AD 17500 VRANJE SRBIJA Radni ka 1 Tel 017 421 121 INSTALLATION USE AND MAINTAINANCE MANUAL CFH XILA ENG_v 1 0...

Page 2: ...ning or operation should be carried out only by qualified personnel Do not use any flammable liquids for ignition process This unit must not be used by people including children with limited physical...

Page 3: ...devices 10 Control panel 11 KEYS 11 LED 11 DISPLAY 12 MENU 12 User menu 1 13 DISPLAYS 13 SETTING PRODUCT POWER 13 MANUAL PELLET LOAD 13 PELLET FEEDER MODIFICATION 13 COMBUSTION FAN MODIFICATION 14 EN...

Page 4: ...essingin order to optimize the painting process and improve the final result Gaskets which make combustion chamber air impermeable They must be checked periodically to prevent the improper combustion...

Page 5: ...2 TOP A Exhaust gases pipe diameter 80 Dimensionsin mm B 3 4 Unit inflow pipe C 1 Unit return pipe D Air intake 50 Details...

Page 6: ...2 7 Heating power to water kW 14 5 4 7 Heating power to ambience kW 3 5 1 4 Efficiency 93 4 95 7 Emissions of CO with 13 of oxygen 0 0131 0 0074 Combustion gas temperature C 126 67 Gas mass flow g s 1...

Page 7: ...value of this fuel LHV 4100 5000 kcal kg Wood pellet used as fuel must have excellent qualitative characteristics such as defined in standards DIN 51731 ONORM M 7135 and EN plus A1 Example of basic d...

Page 8: ...ood pellet accumulates in the combustion chamber while the unit is operational switch off the unit and switch it on with the greater ventilation program If the pellet is still accumulating try a diffe...

Page 9: ...stancefrom combustible material cm ATTENTION After selection of the unit location it is possible to modify unit s height by tilting it sideways and unscrewing legs to reach the proper space from the b...

Page 10: ...certain number of indications that point out the standard for this type of system configuration Always make sure there is an inspection opening I which will enable regular cleaning activities and remo...

Page 11: ...e separated from the outer part of the chimney Figure 2 6 Exampleconnection to the chimney In case of fire in the chimney or exhaust pipe immediately switch off the unit and disconnect it from the pow...

Page 12: ...onnect the power cable to the household powerline and press ON button on the rear side of the unit At the beginning of use unpleasant fumes and odors may occur originating from painted part These inco...

Page 13: ...repeat the loading of the auger every time the hopper is empty 6 Empty the firebox 7 In order to switch on the stove hold ignition key for a few seconds The stove will initiate the check up and igniti...

Page 14: ...ossible for one or more sensors to be interrupted or short circuited This will be detected during the check up phase The failure of these probes could lead to ignition failure continued state of modul...

Page 15: ...o high temperature of flue gases Er07 Encoder error No signal Er08 Encoder error Unable to adjust number of revolutions Er09 Low water pressure Er10 High water pressure Er11 Error due to problems with...

Page 16: ...St Winter InU mode FC Firmware code and revision FYSD01000114 00 00 product without two way radio FYSD01000102 00 00 product with two way radio 395 Manufacturer production code 0Y 0X N B If the value...

Page 17: ...t value default value is 0 After 3 seconds value is stored and the display returns to normal ENABLING CHRONO FUNCTION This sub menu allows activation deactivationof chromo programmingmode Press and ho...

Page 18: ...y for the technical assistance network LEAr Remote control code learning menu Only if the product has two way radio option User menu 2 settingsare shown in the upper display Press K1 key to exit User...

Page 19: ...reach wanted sub menuand pressK5key Gio r n 2 PressK3 K7 keys to select one of three possible programming options _ _ _ _ 1I Mo 3 Press and holdK4 key for3 seconds 00 00 1 Mo 4 Choose the start up tim...

Page 20: ...turn toUser menu 2 settings pressK1key SYSTEM MENU This menu allows access toSystem menu The upper display showstPAr ATTENTION This menu cannot be accessed because it is only for the technical assista...

Page 21: ...ply Preporu uje se da o istite zone opisane iznad pomo u etke koju dobijete sa ure ajem ili usisiva a PA NJA na svakih 3 4 dana obavezno o istite dimne cevi u kotlu Otvorite vrata komore i specijalnom...

Page 22: ...in two ways switching off the rear side power keyor pulling out the power cord from the socket either the wall socket or stove rear side connection plug In case the maintenance operations described i...

Page 23: ...and reset timers by unscrewingtwospark plugs at the back of the unitand pressing both buttons Check air intake opening for blockages Too high environment temperature insufficient temperature reduction...

Page 24: ...ine to shut down and then press and hold ON key for 3 seconds Check the water pressure level in the system Faulty probe Contact service Er11 Clock error Problemswith the internal clock Press and hold...

Page 25: ...t down and then press and hold ON key for 3 seconds Check the primary air openings Check soiling and draft of flue gas pipe Contact service ATTENTION If the recommended solutions fail to remove the pr...