15
Effective 05/04/2012
Unique PMO Plus CP HT Valve Series
Series Sanitary Mixproof Valve Instruction Manual
Think
Top
®,
Digital 8-30 or 110 VAC NO/NC
Automation
Solenoid valves
Up to 3 solenoid valves in each unit.
Type ...............................................................................................3/2 or 5/2 valve (only with one 5/2 valve).
Air supply .......................................................................................300-900 kPa (3-9 bar) (43.5-130.5 PSI)
Filtered air, max. particules or dirt....................................................0.01 mm (0.0004 inch).
Max. oil content ..............................................................................1.0 ppm.
Max. water content .........................................................................0.0075 kg/kg air. (0.02 lb/lb)
Throughput° ...................................................................................Ø2.5mm
Air restriction (throttle function) air inlet/outlet.
Manual hold override.
External air tube connection ...........................................................Ø6 mm or ¼"
Silencer/filter*) .................................................................................Connection possible via Ø6 mm or ¼"
Nominal voltage ..............................................................................24 or 110V
Nominal power ...............................................................................1.0 W.
*) Filter recommended in tropical regions.
Micro environment demand specifications
Temperature
Working:
-4°F to +185°F
IEC 68-2-1/2
Storage:
-40°F to +185°F
IEC 68-2-1/2
Temperature change:
-13°F to +158°F
IEC 68-2-14
Vibration
10-55 Hz, 0.7 mm
IEC 68-2-6
155-500 Hz, 10g
3 x 30 min, 1 octave/min
Drop test
IEC 68-2-32
Humidity
Constant humidity
+104°F, 21 days, 93% R.H.
IEC 68-2-3
Cyclic humidity:
+77°F/+131°F 12 cycles
IEC 68-2-30
(working)
93% R.H.
Protection class
IP67
IEC 529
Input treshold
Voltage/current:
Type 1 input requirements
EN 61131-2
Solenoid signals
Isolation voltage
(1000 + 2 x 117) VAC rms/1 min
EN 61131-2
EMC Directive
89/336/EEC
EN 50081-1, EN 50082-2
UL/CSA Approval
8-30 VAC
UL508-E203255
110 VAC
UL 508-E223664