10.7 Connecting Comms Cables between CUBE and a PODD
CUBE units require a connection to the Alencon PODD device to establish communications
and be controlled. Alencon specifies the use of:
•
CAT5e or better STP cable
•
Male RJ45 connectors, type B crimping
•
22 AWG conductors preferred (24 AWG are acceptable)
Note: CAT cabling should be rated for outdoor use if the cable run is not indoors or enclosed
within conduit.
F
IGURE
18:
C
OMMS
P
ORTS ON THE
CUBE
TO CONNECT TO THE
PODD
OR EXTERNAL
SCADA
Comms cables can be connected as a daisy chain between multiple CUBE units and the PODD.
A cable tester can be used to ensure the connection is sound for all 8 pins through the entire
line.
F
IGURE
19:
M
ULTIPLE
CUBE
S CAN BE DAISY CHAINED TO A SINGLE
PODD