Alencon CUBE: Installation,
Operation, and Maintenance Manual
28 |
P a g e
10.4 Mechanical Install
10.4.1 Selecting Location
The following considerations should be made when selecting the CUBE location.
Indoor/Outdoor:
The CUBE is NEMA 3R rated and can be safely deployed indoors or outdoors
without additional weather protection.
Mounting Pad:
Consult your EPC firm for a specification of the mounting pad construction,
this will likely depend on hurricane regulations, by location.
Temperature:
The CUBE can be stored in any location, where ambient temperature ranges
from -40 to +85 °C.
The CUBE should be operated only when ambient temperature is within -5 to +50 °C.
Clearance:
For safety in operation and maintenance, make sure that the CUBE has enough
clearance around the unit, recommendations are in the table below.
Direction
Recommended Minimum Clearance
Above
15 inches
Below
6 inches
Front (Electrical panel)
36 inches
–
OSHA, NFPA, and NEC requirement.
Back (Air filter access)
24 inches
Right Side (Plumbing access)
36 inches
Left Side
12 inches