![aldes EVEREST XV Installation Instructions Manual Download Page 24](http://html1.mh-extra.com/html/aldes/everest-xv/everest-xv_installation-instructions-manual_2893021024.webp)
24
3.4 Diameters of internal water coil collectors
Caution:
the coils admit a maximum pressure of 8 bar.
Water coils
3-way valve female connection
Models
Coil type
Copper collector
Ø Ext. (Gas inches)
Valve flow factor (Kvs)
DN (mm)
XV 600
1 row
1/2 ˝
1.6
15
XV 1200
1 row
1/2 ˝
1.6
15
XV 1600
1 row
1/2 ˝
2.5
15
XV 2300
1 row
1/2 ˝
2.5
15