6
TMV3 ART 33 Screwed Rev 1
•
Tighten the compression nuts ensuring that the end of the pipe remains in contact with the
filter element.
•
After installation check carefully for leaks.
•
The valve must always be fitted in a location where it is accessible for both test and
maintenance.
Exploded View of ART 33
7.
Commissioning & Adjustment
•
The Albion ART 33 thermostatic mixing valve is supplied factory pre-set at 41--43°C.
However, installation conditions will dictate, that the product be adjusted on site.
•
Prior to commencing commissioning, the following checks should be carried out
•
The designation of the TMV matches the application.
•
The supply pressures and temperatures are within the operating range of the valve.
•
Isolating valves are fitted.
•
The supply temperatures are within the range permitted for the valve and by
guidance information on the prevention of legionella etc.
•
If all these conditions are met, proceed to set the temperature as below: -
•
Remove the protective cap on top of the valve.
•
Back-out the nut using a hexagon wrench:
o
To increase the temperature, turn clockwise
o
To decrease the temperature, turn anti-clockwise