Albion TMV3 Installation & Operating Manual Download Page 6

6

TMV3 ART 33 Screwed Rev 1

• 

Tighten the compression nuts ensuring that the end of the pipe remains in contact with the  

 

filter element.

• 

After installation check carefully for leaks.

• 

The valve must always be fitted in a location where it is accessible for both test and  

 

 maintenance. 

Exploded View of ART 33

 

7.  

Commissioning & Adjustment

• 

 

The Albion ART 33 thermostatic mixing valve is supplied factory pre-set at 41--43°C.    

 

However, installation conditions will dictate, that the product be adjusted on site.

• 

 

Prior to commencing commissioning, the following checks should be carried out

 

• 

The designation of the TMV matches the application.

 

• 

The supply pressures and temperatures are within the operating range of the valve.

 

• 

Isolating valves are fitted.

 

• 

The supply temperatures are within the range permitted for the valve and by  

 

 

 

guidance information on the prevention of legionella etc.

• 

 

If all these conditions are met, proceed to set the temperature as below: -

 

 

• 

Remove the protective cap on top of the valve.

 

 

• 

Back-out the nut using a hexagon wrench:

 

 

 

To increase the temperature, turn clockwise

 

 

 

To decrease the temperature, turn anti-clockwise

Summary of Contents for TMV3

Page 1: ...Albion Valves UK Ltd www albionvalvesuk com Email sales albionvalvesuk com Tel 01226 729900 TMV3 ART 33 Screwed Rev 1 TMV3 Installation Operating Manual ART 33 Screwed Thermostatic Mixing Valve...

Page 2: ...e Estates NHSE Health Guidance Note HGN makes reference to three types of valve Type 1 o Having both flow control and user adjustment of mixed water temperature Type 2 o Having flow control and pre se...

Page 3: ...terial Directory 3 Technical Specification Factory Temperature Setting 42 C Temperature Adjustment Range 30 C 48 C Mix Temperature Stability 2 C Cold Water Supply Temperature 5 C 25 C Hot Water Supply...

Page 4: ...Bar 10 10 Hot Cold Pressure Bar 1 0 5 0 0 2 1 0 Hot Supply Temperature C 55 65 55 65 Cold Supply Temperature C 5 20 5 20 Mix Water Temperature C Maximum 46 Maximum 46 Temperature Differential C 12 12...

Page 5: ...lve assembly bores are free of debris and the end sealing faces are clean Check the two tailpieces and confirm they are complete with union nuts and compression nuts with olives Insert the sealing was...

Page 6: ...at the product be adjusted on site Prior to commencing commissioning the following checks should be carried out The designation of the TMV matches the application The supply pressures and temperatures...

Page 7: ...dition and reset it to the correct temperature 0 2 C Do not set a valve with a lowered temperature as this will not provide consistent operation After adjustment replace the cap to lock the valve in p...

Page 8: ...results e g 1 C record the change and before re adjusting the mixed water temperature carry out the following checks All in line or integral filters are clean Any in line or integral non return valve...

Page 9: ...months as a minimum 9 TMV Cleaning Instructions Most domestic water supplies contain calcium which will separate out when the water is heated in a system The degree and speed of scaling may vary depe...

Page 10: ...ease components Please ensure that the grease is WRAS approved Remove the O ring Clean the valve body and headwork using a propriety de scaler Thoroughly rinse the body and headwork in clean water Car...

Page 11: ...12 month guarantee of the ART 33 TMV The guarantee offered covers manufacturing material defects The guarantee will be void should the product not have been fitted and maintained as per Albion Valves...

Page 12: ...you can rest assured that if it comes from Albion it has been designed and manufactured to deliver optimum performance and is accredited with the necessary approvals Our in house quality department a...

Reviews: