4
TMV3 ART 33 Screwed Rev 1
5.
Conditions of Normal Use (TMV3)
Water Regulations
•
The thermostatic mixing valve must be installed in accordance with the regulations of the
local water company and the Water Supply (Water Fittings) Regulations 1999.
Operating Pressure Range
High Pressure
Low Pressure
Maximum Static Pressure (Bar)
10
10
Hot & Cold Pressure (Bar)
1.0 – 5.0
0.2 – 1.0
Hot Supply Temperature (°C)
55 – 65
55 – 65
Cold Supply Temperature (°C)
5 – 20
5 – 20
Mix Water Temperature (°C)
Maximum 46
Maximum 46
Temperature Differential (°C)
12
12
•
Thermostatic Mixing Valves are temperature sensitive devices and must not be subjected
to extreme temperatures, either hot or cold, in use for installation.
•
Valves operating outside these conditions of use cannot be guaranteed to operate
as TMV 3 valves.
•
Designations of Use
HP - B / S / W / T44
LP - B / S / W
6.
Installation & Assembly