55
5.1.2 Parameter selection mode
• By pressing RESET switch for 1 touch it is possible to select param
-
eters.
• By pressing RESET switch for more than 5 sec., the modification
menu is entered then the actual value is shown.
5.1.3 Parameter changing mode
• By moving DHW knob, the desired value can be chosen (SET word
appears on LCD screen).
• If RESET switch is pressed for a time greater than 5 sec., the modi
-
fication is memorized and the system returns to PARAMETER SE
-
LECTION MODE with the following parameter already selected.
By moving the CH knob, it is possible to exit PARAMETER MODE.
After 2 minutes without performing anything through DHW knob, an au-
tomatic exit is forced and boiler will go back to its normal operating con-
dition.
HARMONY_D USERS INSTALLATION AND SERVICE MANUAL
43
By rotating DHW knob P1 value can be set.
To save the selected P1 value, leave DHW knob in the selected position and press
RESET switch for 5 sec.
* Since the display has two digits, P letter and corresponding numbers are visualized
alternatively.
5.1.2 Parameter selection mode
By pressing RESET switch for 1 touch it is possible to select parameters.
By pressing RESET switch for more than 5 sec., the modification menu is entered then
the actual value is shown.
5.1.3 Parameter changing mode
By moving DHW knob, the desired value can be chosen (SET word appears on LCD
screen).
If RESET switch is pressed for a time greater than 5 sec., the modification is memorized
and the system returns to PARAMETER SELECTION MODE with the following
parameter already selected.
By moving the CH knob, it is possible to exit PARAMETER MODE.
After 2 minutes without performing anything through DHW knob, an automatic exit is forced
and boiler will go back to its normal operating condition.
Table 6 Parameter Adjustment
Locally
on board
Description
Value
00
Value
01
Value
02
Value
03
P1
Ignition capacity
Adjustable 0 - 63%
P2
Gas type
MTN
LPG
3rd
4th
P3
CH off time
Adjustable 0 - 255 sec.
P4
CH max capacity
Adjustable 0 - 100%
P5
Range CH
Normal
Reduced
P6
DHW switch off temp
65°C
Set point
P7
LED strip configuration
(#12 leds)
Always ON * ON when flame
is ON *
Always
OFF
** = Since the display has two digits, if parameter is greater than 99, the first digit is displayed in turn with the other two digits:
e.g. if parameter = 136: 01 is displayed in turn with 36
* When LCD backlight is ON, LED strip is switched OFF independently from LED strip configuration value.
5.1.4
PARAMETERS’ ADJUSTMENT
Authorized service can change seven of the parameters related to boiler operation via using
the reset button and knobs on the control board.
1)
Ignition Gas Pressure:
It controls the outlet gas pressure of gas valve during ignition
period. By using Table 6, adjustment can be done as percentage. Default setting of P01