General:
01905 823 298
|
www.akw-ltd.co.uk
14
14
PUMP
Se
TTI
ng
S
Pump Settings
When power is applied to the pump, the display will briefly indicate the model and software version of the pump, the pump will
then enter standby mode.
00
M11
01
M17
02
M20
Standby Mode
The ‘RUn’ led will be lit, indicating mains voltage present.
The display will indicate the ‘run-on timer’ setting in seconds (factory default 20)
Adjusting the Settings
SENSOR TYPE
from Standby, hold and release TeST button until
RUn and DelaY leD’s flash
TYPe:
00
on/off (grounded input)
01
600 pulses per litre
02
1000 pulses per litre (Default)
03
2200 pulses per litre
Up - Press and release RUn button
Down – Press and release DelaY button
exit to calibration - Press and release TeST button
CALIBRATION
Default setting:
50
Range adjustment:
00 - 99
To change the value:
Up - Press and release RUn button
Down – Press and release DelaY button
exit to auxiliary switch type - press and
release TeST button
AUXILIARY SWITCH TYPE
TYPe:
00
latching
01
Momentary
Up - Press and release RUn button
Down – Press and release DelaY button
exit to standby - Press and release TeST button
START DELAY
from Standby, press and release DelaY button to
increment value
Default setting:
05
Range adjustment:
01 - 99
exit to standby - press and release RUn button
RUN-ON TIME
from Standby, press and release RUn button to
increment value
Default setting:
20
Range adjustment:
01 - 99
TEST MODE
from Standby, press and release TeST button
Test Mode sequence will start:
1. The start delay value will count down to
0
2. Pump will start
3. The run value will count down to
0
4. Pump will stop
5. Test completed - the Pump will revert to
Standby mode
This test can be carried out with or without water
present and the sensor fitted or not
Testing the Pump