9.5.- Pump down function 

This function prevents compressor problems caused by movement of the refrigerant, using a stop/start technique of 
the unit controlled by liquid solenoid, the low pressure switch and the compressor.
For this feature to be active, the auxiliary relay must be set as "Pump down" (

P6=1

).

SHUTOFF

When temperature probe 1 reaches the set point value (

SP

), the AUX 1 relay is deactivated by closing the liquid 

solenoid.
Since the compressor is still running the evaporator pressure drops suddenly. When it reaches a specific point, the 
low pressure switch is activated, changing the state of digital input 1, and the controller stops the compressor.
This manoeuvre isolates the refrigerant from the compressor crankcase, preventing serious damage on start-up.
In case of low pressure switch failure, the controller stops the compressor after the safety time set at 

P15,

 showing 

the message "

Pd

", but it will continue to function normally. (informative message, does not affect the equipment 

operation).
If time 

P15

 is 0 (default value), the compressor will not stop until the low pressostat is activated, but it will display 

the “

Pd

” message after 15 minutes.

DOES NOT

 activate the alarm relay or the sound alarm, it is only shown on the display.

STARTUP

When temperature probe 1 reaches the set point value plus the differential (

SP+C1

), the AUX 1 relay is activated 

(ON), opening the liquid solenoid. This causes the pressure in the evaporator to increase, disabling the low pressure 
switch. The controller detects this change and starts the compressor.
If a period of time has elapsed (determined by 

P14

) after the liquid solenoid is opened (AUX 1 relay set to ON), the 

low pressostat will not be deactivated, the controller will once again close the solenoid (AUX 1 relay set to OFF) 
and  the “

LP

”  message  will  be  displayed. This  manoeuvre  will  be  repeated  every  2  minutes  indefinitely  until  the 

pressostat is deactivated and the installation reverts to its normal operation.
If time 

P14

 is 0 (default value), the solenoid will stay open until the low pressostat is deactivated, but it will display 

the “

LP

” message after 3 minutes.

DOES NOT

 activate the alarm relay or the sound alarm, it is only shown on the display.

STAND-BY

If  the  pump-down  function  is  active,  some  time  may  elapse  from  the  time  the  stand-by  function  starts  until  the 
controller stops. This is because certain control phases of the system cannot be stopped.

ON

Liquid 

solenoid

Low pressure 

switch

Pressure 
switch fault

Pressure 
switch fault

Compressor

Evaporator 

pressure

ON

ON

+

P15

P14

OFF

OFF

OFF

AUX 1

Digital

Input

COMP.

Time

SP

SP

SP+C1

SP+C1

Summary of Contents for AKO-15690

Page 1: ...AKO 1569x AKO 1569x EVC PROPlus 3PH BASIC Electronic Panel GB 1569H042 Ed 03 User Manual...

Page 2: ...these regulations Rigorouslyfollowtheinstructionsdescribedinthismanual Inordertoextendthelifetimeofourproductstothemaximum thefollowingpointsmustbeobserved Do not expose electronic equipment to dust...

Page 3: ...C and 20 C if the NTC probe is extended up to 1 000 m with minimum 0 5 mm wire the maximum deviation will be 0 25 C Wire for probe extension ref AKO 15586 IMPORTANT The AUX 1 AUX 2 and AUX 3 relays ar...

Page 4: ...emovecover B Using the included template make 4 holes in the wall and fasten the unit to the wall using the supplied screws Makeaholeinthebottomoftheboxtopassthecablesthrough andasuitableglandshouldbe...

Page 5: ...tor guard Q1 according to the obtained value The setvalueshouldneverbehigherthantheconsumptionindicatedbythemanufacturer 11 5 A A 1 2 I O 1 0 16 10 1 6 Q1 AKO 15690 1 2 3 AKO 15690 1 2 3 EVC AKO 15699...

Page 6: ...1569H042 Ed 03 A B C C C 6 D Remove the front trims A and screw the cover on using the included screws B Theninstallthetrimsagain ALL MODELS...

Page 7: ...he panel up Powersupplyvoltagesandfrequencieswillbetheonesthatfigureinthe Technicalspecifications section Checkthattherearenoloosepartsorforeignbodiesonconnectionsorswitchgear Checkthatthereisnodustor...

Page 8: ...ing it for 5 seconds allows changing the SETPOINTtemperature Pressing it for 5 seconds activates or deacti vatestheCONTINUOUSCYCLE Pressing it for 5 seconds the quick setup menu is accessed Pressing i...

Page 9: ...ctivates alarm relay and sound alarm Alternating with temperature External alarm activated by digital input p 18 Activates alarm relay and sound alarm Alternating with temperature Severe external alar...

Page 10: ...frost circuit breaker FM Operation circuit breaker Q1 Compressor motor guard Q3 Evaporator fan motor guard K1M Compressor contactor K2M Defrost contactor K4M Evaporator fan contactor T2 EVC Transforme...

Page 11: ...ne high low pressure controller AKO 15690 1 2 3 AKO 15690 1 2 3 EVC Separate Low pressure controller per AC input AKO 15690 1 2 3 AKO 15690 1 2 3 EVC Pressure controller equivalence HIGH LOW 16 16 17...

Page 12: ...requency Time that must elapse between the starting of each defrost see page 15 d1 Maximum defrost duration The defrost will end after this time has elapsed since it started F3 Fan status during defro...

Page 13: ...he temperature in probe 1 reaches the set point value SP plus the probe s differential C1 the compressor activates and makes the temperature drop When the set point value SP is reached thecompressorst...

Page 14: ...ill operate according to the average performance of the last 24 hours taking into account the number of starts and stops and the average time in each state stop start C6 3 The compressor will run as s...

Page 15: ...termination The defrost will terminate if The temperature programmed in parameter d4 has been reached in probe 2 Probe 2 must be activated P4 In the event of probe 2 failure defrosting will be complet...

Page 16: ...account parameters F2 to F5 Parameter F2 defines the status of the fans during compressor stops Parameter F3 defines the status of fans during defrost Parameter F4 defines the fan start up delay afte...

Page 17: ...or the sound alarm it is only shown on the display STARTUP When temperature probe 1 reaches the set point value plus the differential SP C1 the AUX 1 relay is activated ON opening the liquid solenoid...

Page 18: ...n probe 1 reaches 10 degrees and is disabled when it reaches 8 degrees External alarm severe external alarm Displays the message AE external alarm or AES severe external alarm when the digital input c...

Page 19: ...rature alarm A5 Delays activation of maximum A1 and minimum A2 temperature alarms from the moment temperature probe 1 reaches the set value Delay of external alarm activation A6 Delays the activation...

Page 20: ...ly Connect the programming key in the parameter server connector Connect the power supply for the programming key Press the READ key on the programming key Disconnect the device programming key Transf...

Page 21: ...PC Up to 127 units can be connected to a PC with AKONet AKO 5010 or to the AKO 5011 web server Each of these unitsshouldhaveadifferentMODBUSaddress thatisdefinedusingtheP5 Using the AKONet software it...

Page 22: ...Thisfunctionconfiguresalltheunit sparameterstoitsdefaultvalues i e asitleavesthefactory In order to return the computer to its initial settings go to the programming menu and set parameter P3 to 1 The...

Page 23: ...Protectiondelaytime valueoftheoptionselectedinparameterC4 Page14 min 0 0 120 C6 StatusofCOMP relaywithprobefault Page14 0 OFF 1 ON 2 Averagebasedonlast24hourspriortoprobefault 3 ON OFFasprog C7andC8...

Page 24: ...1 YES Firstdefrostasperd6 0 0 1 d6 Defroststartdelayonequipmentstart up Page16 min 0 0 255 d8 Calculatedtimebetweendefrostperiod Page16 0 Totalactualtime 1 Sumoftimesthecompressorison 0 0 1 d9 Driptim...

Page 25: ...Alarmrelaypolarity 0 RelayONinalarm OFFnoalarm Page19 1 RelayOFFonalarm ONwithnoalarm 0 0 1 A10 TemperatureAlarmDifferential A1andA2 Page18 C F 0 1 1 0 20 0 A12 Dooropenalarmdelay ifP10orP11 1 Page19...

Page 26: ...sec 0 0 120 P15 Maximumpumpdowntime Page17 0 Disabled min 0 0 15 P22 Coldroomlighttimer Page16 min 0 0 999 P23 Stopfansandcompressoronopeningdoor Page14 0 No 1 Si 0 0 1 P24 Startupdelayforfansandcompr...

Page 27: ...cisionoftheNTCprobeat25 C 0 4 C InputforNTCprobe AKO 14901 Maximuminputpowerintheoperation 30VA Workingambienttemperature 5 Cto40 C Storageambienttemperature 30 Cto70 C Overvoltagecategory IIs EN61439...

Page 28: ...ials that might vary slightly to those described in our Technical Sheets Updated information is available on our website AKO ELECTROMEC NICA S A L Avda Roquetes 30 38 08812 Sant Pere de Ribes Barcelon...

Reviews: