1565H041 Ed.03
9.2.- Defrost control
DEFROST
DEFROST
DRIP TIME
FAN START UP DELAY
"DEF” MESSAGE
CONTROL
CONTROL
time
ºC
Max. B
C
A
SP
SP+Dif.
D
DEFROST
DEFROST
DRIP TIME
FAN START UP DELAY
"DEF" MESSAGE
CONTROL
CONTROL
Description
Parameter
A
Time between two defrost starts
Defrost frequency
B
Maximum defrost duration
Defrost duration
C
Maximum duration of the defrost message
Message duration
D
Final defrost temperature by probe 2
Defrost final temperature
SP
Temperature set point
Set point (SP)
Dif.
Temperature set point differential
Sensor 1 differential
9.2.- Defrost control
*In the panels
AKO-15658
/
15659
, the liquid solenoid is controlled instead of the compressor.
Defrost start
Defrost will start if:
Ÿ
The time programmed in the
Defrost frequency
parameter has passed since the start of the last defrost.
The parameter
Defrost mode
defines how this time is counted:
ž
Frequency:
Total time passed between defrost starts.
ž
Compressor sum:
Total time of the compressor/solenoid* operating between defrost starts.
ž
Real Time Clock:
Defrost starts when one of the times programmed in the
Defrost 1
to
8
on the
u
menu is reached. (The defrost frequency is not taken into account).
Ÿ
We press the
N
key for 5 seconds.
End of defrost
The defrost stops if:
Ÿ
The temperature programmed in the
Defrost final temperature
has been reached in probe 2 (this requires
having a defrost probe connected to S2). In the event of probe 2 failure, defrosting will be complete once the
maximum time has elapsed (
d1
).
Ÿ
The time configured in the
Defrost duration
has passed (maximum defrost duration). The
I
icon is shown on
the display if the
Signals end defrost time
parameter is configured in “Yes”.
Ÿ
We press the
N
key for 5 seconds.
REMARK:
If the
Defrost duration
is configured to 0, no defrosts are carried out.