akira AC-F30HG Service Manual Download Page 34

       

                                       

  34

 

 
Model No: AC-F30HG 
Version 1.0 
 

   

 
 

2.  Protecting of compressor high-pressure: 

When detect protecting of high-pressure for 3sec, turn off load except water pump, shield all 
button and signal of remote control, timer indicate light will flashing; when detect no protecting 
of compressor high-pressure for 6sec, remove shielding function, timer indicate light will 
flashing, after press ON/OFF to turn off unit, turn off indicate light, When press ON/OFF, then 
restart running. 
 

3.  Protecting of compressor low-pressure: 

a.  After compressor start for 3min, begin to detect signal of low-pressure switch, if detect that 

low-pressure switch turn off for 3min, then the unit stop, timer indicate light will flashing, 
after 3min the unit renew to run automatically; if protecting of low-pressure switch 
continually appear times, timer indicate light will flashing, and the unit can not renew 
automatically, in order to awoke user that the unit leak refrigerant; after press ON/OFF, the 
unit turn off, press ON/OFF again, renew to run; 

b.  When frosting act, the unit do not detect signal of low-pressure switch. After finish frosting 

for 10min, to start to detect; 

c.  At the same time, press the force key and auto key of controller, shield to detect signal of 

low-pressure switch, so that reclaim refrigerant, after 6min, renew detecting automatically, 
or press ON/OFF key to turn off the unit, after press ON/OFF key again, renew detecting; 

d.  When heating act, if T

out

 

 -0

o

C, shield detect low-pressure switch; 

e.  When heating act, compressor run, and the outdoor fan motor stop (protecting of avoid high 

temperature), shield detect low-pressure switch, after the outdoor fan motor renew to run, 
start to detect signal of low-pressure switch; 

f.  When compressor stop, if detect that low-pressure switch turn off for 30sec, then the unit 

turn off, timer indicate light will flashing, can not renew automatically. After press 
ON/OFF key, the unit turn off, if press ON/OFF key, then renew to run unit. 

 
4.  Protecting of discharge pipe high temperature: 

After compressor starts, if detect that T

con

 higher than T2 (T2=120

o

C, 125

o

C, 130

o

C, different 

jump-thread) for 30sec, or discharge pipe temperature sensor have any trouble, timer indicate 
light flash. 
The unit stops as if T

in

 reach T

set

After compressor stops for over 3min, if T

con 

< 90

o

C, then the unit renew to run. If this 

protecting phenomenon happens twice continually, and the unit can not renew automatically, 
timer indicate light flashes. Press ON/OFF key to turn off the unit, press ON/OFF key again, if 
T

con

 < 90

o

C, the unit can run in set mode, otherwise timer indicate light still flashes. 

 

5.  Protecting of indoor exceed high temperature: 

When heating act, if detect T

eva

 

 56

o

C for 5 sec, the outdoor unit fan motor stops, if T

eva

 

 51

o

C, the outdoor unit fan motor startups. If T

eva 

 100

o

C, the indoor unit fan motor 

automatically turn to high speed; If T

eva

 

 48

o

C, the indoor unit fan motor turn to old set speed. 

 

Все каталоги и инструкции здесь:

 http

:

//splitoff.ru/tehn-doc.html

Summary of Contents for AC-F30HG

Page 1: ...Air Conditional Service Manual http splitoff ru tehn doc html...

Page 2: ...Model No AC F30HG Version 1 0 2 Model AC F30HG http splitoff ru tehn doc html...

Page 3: ...3 Model No AC F30HG Version 1 0 CONTENTS SPECIFICATIONS 4 OUTLINE DIMENSIONS 6 EXPLODED VIEW PART LIST 8 INSTALLATION GUIDE 13 CIRCUIT DIAGRAM 28 PCB FUNCTION MANUAL 29 http splitoff ru tehn doc html...

Page 4: ...0B Motor fan speed r min 385 355 315 Output power W 50 Working capacitor mui F 4 5 Fan type piece Centrifugal fan 1 Diameter length mm 378 130 evaporator Aluminum fin copper tube Row fin distance mm 2...

Page 5: ...60 Fan motor speed rpm 780 Capacitor mui F 3 Fan type piece Axial fan 1 Fan Fan diameter mm 455 Model HZOPS B3 0 2 4Mpa or YK 3 0 2 4Mpa Cutoff pressure 3 0 0 15Mpa High pressure switch Restart pressu...

Page 6: ...NIT Right knock out hole Grille Front panel Controller Filter Air intake grille Gas pipe Liquid pipe Drainage hose Left knock out hole Rear right knock out hole Rear left knock out hole Right side Fro...

Page 7: ...7 Model No AC F30HG Version 1 0 OUTLINE AND DIMENSIONS OUTDOOR UNIT Handle Gas valve assy Wire hole Liquid valve assy Grille 840 http splitoff ru tehn doc html...

Page 8: ...8 Model No AC F30HG Version 1 0 EXPLOSIVE VIEW AND PARTS LIST INDOOR PANEL http splitoff ru tehn doc html...

Page 9: ...1 1 16 Cable crossing Loop 76514425 2 17 Fan Motor LN50B 15014205 1 18 Cable pressed Plate 01384201 1 19 Rear Plate 01304241 1 20 Protective Cover 22244231 1 21 Left Side Plate 01304201 1 22 Top Cover...

Page 10: ...tor 4 5uF 450VAC 33010012 1 42 Terminal Board T5A0A 77 42011209 1 43 Air Louver 10514212 6 44 Air Outlet Assy 20004201 1 45 Air Guider 10514213 6 46 Swing Motor 15214215 1 47 Panel Assy 20004215 1 48...

Page 11: ...11 Model No AC F30HG Version 1 0 OUTDOOR UNIT http splitoff ru tehn doc html...

Page 12: ...07245201 1 14 4 Way Valve 43000310 1 15 Gas liquid Separator 07255251 1 16 Isolation Sheet Assy 01235253 1 17 Condenser Assy 01105035 1 18 Top Cover Assy 01255260 1 19 Electric Box 01405201 1 20 Cable...

Page 13: ...not increase noise and vibration 4 Select a place easy to drain water and connect with the outdoor unit 5 Make sure there is enough space for maintenance and make sure the distance between the unit a...

Page 14: ...iling opening and suspension bolt M10 pitch dimension Note Installation is possible with a ceiling dimension of 890 marked with can be 910 but the ceiling panel overlapping dimension must be 20mm or m...

Page 15: ...unit and on the paper pad for installation d Fix the paper pad to the unit with screws 3 2 Refer to diagram 3 adjust the unit to the right position for installation 3 Check if the unit is horizontall...

Page 16: ...ng machine oil and initially tighten by hand 3 or 4 turns Check the pipe connector for gas leaks then insulate it as shown in the drawing below Use sealing pad 11 to wrap joint between gas pipe and th...

Page 17: ...ipe d To keep the drainage hose from sagging keep space between hanging hooks at 1 1 5m e Use the attached drainage hose and clamp Insert the drainage hose into the drainage socket up to the grey tape...

Page 18: ...whose gauge is suitable for the operating capacity of the unit 2 After finishing installation check if drainage water flows smoothly a Add approximately 600 cc of water to the drainage trough through...

Page 19: ...t must be replaced by the manufactory or its service agents or a similarity qualified person in order to avoid a hazard Wiring of unit and the controller Wiring of the indoor unit Remove the control b...

Page 20: ...swing flap motor on the panel temporarily to the book of the indoor unit 2 Positions b Temporarily hang the remaining 2 latches to the hooks on the sides of the indoor unit be careful not to let the...

Page 21: ...21 Model No AC F30HG Version 1 0 Fig 4 Precautions 1 Improper screwing of the screws may cause the troubles shown in Fig 5 http splitoff ru tehn doc html...

Page 22: ...wing the screws readjust height of the indoor unit body Refer to Fig 6 After fixing be sure no gap left between the ceiling and the panel 3 Wiring of the decoration panel Connect the joints for swing...

Page 23: ...rvicing space can be well ensured Places where strong wind can not blow directly to outdoor unit Outdoor unit installation 1 Install the unit firmly with combination of M10 or more bolts and nuts on t...

Page 24: ...ing according to the WIRING DIAGRAM 2 A circuit breaker capable of shutting down power supply to the entire system must be installed 3 Earth properly 4 All wiring must be performed by a skilled electr...

Page 25: ...wer supply terminal board 8p and the rubber wire 5 cords to L1 L2 L3 N of the power supply terminal board 8p accordingly For cooling heating type Connect the rubber wire 5 cords to the power supply te...

Page 26: ...ss 1 0 button b Press MODE button select COOL HEAT FAN etc to test whether it operates mormally 3 Emergency operation a When the batteries fail or when the remote controller is missing operate as show...

Page 27: ...e flow smoothly Condensate water may drip Does the power supply voltage correspond to that shown on the nameplate The unit may malfunction or the components burn out Are wiring and piping correct The...

Page 28: ...28 Model No AC F30HG Version 1 0 CIRCUIT DIAGRAM http splitoff ru tehn doc html...

Page 29: ...ve c Compressor d Water pump e Fresh air fan motor f Anion creator 3 The parameter to be input a The ambient temperature of the indoor unit shorten form is Tin b The evaporator temperature of the indo...

Page 30: ...Tset 2o C drying mode act compressor indoor unit fan motor run the indoor unit fan motor runs in low speed If Tset 2o C Tin Tset 2o C compressor indoor unit and outdoor run for 6 min then stop for 3 m...

Page 31: ...e compressor is stop guider turn into horizontal the indoor unit fan motor runs in low speed The conditions of beginning defrosting After the unit continue heating for 44min and detect Tcon 8o C for 1...

Page 32: ...he Tset will be increased 1o C automatically and it will be increased 1o C automatically after 2hour from the beginning then the unit runs in this temperature If it is heating in 1hour of the beginnin...

Page 33: ...ndicate light it turn on when the unit is turned on and turn off when the unit is turned off It will be flashing when Defrosting avoiding the cold wind protecting of full water tank b Timer light it t...

Page 34: ...ess ON OFF key again renew detecting d When heating act if Tout 0o C shield detect low pressure switch e When heating act compressor run and the outdoor fan motor stop protecting of avoid high tempera...

Page 35: ...ulsory heating act turn off all load except for 4 way valve the indoor unit fan motor stops 1min later when fanning act the indoor unit fan motor stops 1min later e In water full protection if detect...

Page 36: ...estart function Memory content mode swing set temperature set speed The unit can restart automatically according to memorizing previous state after break electricity compressor will 3min delay in firs...

Reviews: