Model No: AC-F30HG
Version 1.0
Drainage pipe
1. 1.Installation of drainage pipe.
a. The diameter of the drainage pipe should be greater than of equal to the diameter of the
connecting pipe [vinyl tube, pipe size: 25mm (outer dimension)]
b. Keep the drainage pipe short and sloping downwards at a gradient of at least 1/100 to
prevent air pockets from forming.
c. If the drainage hose cannot be sufficiently set on a slope, add a drainage-raising pipe.
d. To keep the drainage hose from sagging, keep space between hanging hooks at 1 1.5m.
e. Use the attached drainage hose and clamp. Insert the drainage hose into the drainage
socket up to the grey tape. Tighten the clamp until the screw head is less than 4 mm
from the hose.
f. Wrap the big sealing pad around clamp of the drainage hose to insulate.
g. Insulate the drainage hose inside the room.
Precautions for drainage raising pipe
1. Install the drainage-raising pipe at a height of less than 280 mm.
2. Install the drainage-raising pipe at a right angle to the indoor unit and no more than 300 mm from the
unit.