3. Continuity Test

. Refering to the picture of the connector above. Disconnect the module from the green terminal block 

then using a multimeter: 

A. Measure the resistance between A-B. 

B. Measure the resistance between A-C. 

C. Measure the resistance between A-D. 

D. Measure the resistance between B-C. 

E. Measure the resistance between B-D. 

F. Measure the resistance between C-D 

Recheck A-B with a multimeter. The value should be near C-D. A-B should not be infinite otherwise it will return a sensor 
error. Please send these testing results t

[email protected]

 and include the length of the rope and the serial # which is 

located on the side of the black electronics module. 

Notes on the Impedance and Sensitivity of the ropeWater Sensors 

T

he rope sensors come with the impedance value in the package. If they don’t have this then this is how it is calculated: 

 

 

Regarding the sensing impedance, please find below the instruction to calculate it for more custom value. 
Sensing Impedance = [ (Rope resistance between pin 1 and 2 + Rope resistance between pin 3 and 4) / 2] / Water Rope 
length in meter 
Pin 1 is the red wire on the green phoenix connector and pin 4 is the yellow wire.

 

Summary of Contents for ropeWater

Page 1: ...www AKCP com ropeWater Sensor Copyright 2014 AKCess Pro Co Ltd...

Page 2: ...e standard water detectors which measure the resistance of water The detector provides feedback to the web based interface which will indicate the presence absence of water with a Normal Alert or Crit...

Page 3: ...nsorProbe or securityProbe s 8 RJ 45 Intelligent sensor ports or any of the securityProbe 5E s E sensor8 expansion module ports o Can be extended up to 100 feet or 30 meters using normal CAT5 6 LAN ca...

Page 4: ...page Now we will cover the settings that are specific to your sensor Status If the sensor is offline the status is No Status If the sensor is online and there is no water detected the status is Norma...

Page 5: ...ropeWater sensor shows the Normal status in Summery page after connecting the sensor and when water is detected is will show Crtical in this page and the syslog Use the Sensors page and the Water Det...

Page 6: ...attery acid only Tested with 40 concentrate Sulphuric acid H2SO4 Mounting the ropeWater sensor We recommend using any standard plastic U clip or half U clip with the adhesive base as shown in these tw...

Page 7: ...critical condition back to the normal or non critical condition Trouble Shooting the ropeWater sensor The rope type sensors are sensitive to EMI and also metallic or conductive items and surfaces So t...

Page 8: ...ropeWater Detector 8 2 Check the tail connector contacts if they are not damaged After checking reconnect them together as shown in the picture below...

Page 9: ...will return a sensor error Please send these testing results to support akcp com and include the length of the rope and the serial which is located on the side of the black electronics module Notes o...

Page 10: ...and the status should change to critical Plug the Green terminal block back in place then wait for the Red LED to turn off Then wet the yellow or blue cable with water not the Orange cable Notes on th...

Reviews: