AKCP ropeWater Manual Download Page 4

 

 

ropeWater Detector 

 

- 4 - 

b) 

Now point your browser to the IP address of the unit (default, 192.168.0.100). Next you need 

to login as the administrator using your administrator password (default is “public”). You will then 
be taken to the summary page. 

c)

 From the summary page you need to select the sensors tab. The layout of the next page will 

vary depending on your unit so please refer to your 

unit’s manual. 

d) 

You should now be able to setup the thresholds for your sensor. The low critical, low warnings, 

normal, high warnings, high critical values can be set from this page. 

Now we will cover the settings that are specific to your sensor. 

Status:

 If the sensor is offline, the status is No Status. If the sensor is online, and there is no 

water detected, the status is Normal. If water is detected, then the status is Critical. If at any time 
communications with the ropeWater sensor are lost, the status of the ropeWater sensor is 
changed to Sensor Error. 

 

Configuring the ropeWater sensor on a sensorProbe unit 

The ropeWater sensor shows 

the “Normal” status in Summery page after connecting the sensor.  

 

Use the Sensors page and the Water Detector sensor settings in the sensorProbes web interface 
for configuring the ropeWater sensors settings. 

 

The ropeWater 

sensor shows the “Critical” status in the Summery page after detecting water. 

Summary of Contents for ropeWater

Page 1: ...www AKCP com ropeWater Sensor Copyright 2014 AKCess Pro Co Ltd...

Page 2: ...e standard water detectors which measure the resistance of water The detector provides feedback to the web based interface which will indicate the presence absence of water with a Normal Alert or Crit...

Page 3: ...nsorProbe or securityProbe s 8 RJ 45 Intelligent sensor ports or any of the securityProbe 5E s E sensor8 expansion module ports o Can be extended up to 100 feet or 30 meters using normal CAT5 6 LAN ca...

Page 4: ...page Now we will cover the settings that are specific to your sensor Status If the sensor is offline the status is No Status If the sensor is online and there is no water detected the status is Norma...

Page 5: ...ropeWater sensor shows the Normal status in Summery page after connecting the sensor and when water is detected is will show Crtical in this page and the syslog Use the Sensors page and the Water Det...

Page 6: ...attery acid only Tested with 40 concentrate Sulphuric acid H2SO4 Mounting the ropeWater sensor We recommend using any standard plastic U clip or half U clip with the adhesive base as shown in these tw...

Page 7: ...critical condition back to the normal or non critical condition Trouble Shooting the ropeWater sensor The rope type sensors are sensitive to EMI and also metallic or conductive items and surfaces So t...

Page 8: ...ropeWater Detector 8 2 Check the tail connector contacts if they are not damaged After checking reconnect them together as shown in the picture below...

Page 9: ...will return a sensor error Please send these testing results to support akcp com and include the length of the rope and the serial which is located on the side of the black electronics module Notes o...