Condensation
protection
(only available on installations with cooling radiant control). Enables to select the
protection level against condensation: Very high, high, medium (by default), low and very low. If necessary, it can be
activated for 1h.
•
Battery temperature.
Allows to set the working limit temperatures of the cooling and heating batteries of the fancoil
module ((AZDI6ZMOFAN [C/R]), provided that they are installed.
-
Heating battery: To set the mínimum temperature for the water of the heating battery. (Default preset 37 ˚C)
-
Cooling battery: To set the maximum temperature for the water of the cooling battery. (Default preset 17 ˚C)
•
Reset system
(only available for master thermostat Blueface)
.
Resets the system and returns to factory settings. To
reconfigure the thermostats, please check
Think
•
Information.
It provides information about the zone, the system, the devices and the Webserver.
•
Radio channel.
It activates/deactivates the Wireless association module of the system.
ZONE SETTINGS
Important:
In Think thermostats, press
to confirm and
to return to the previous menu/screen.
•
Zone address
(only available from remote zones, in zones controlled by Lite thermostats)
. Shows and allows to modify
the zone number assigned among the availables.
•
Associated outputs.
It displays and allows you to select the control outputs associated with the thermostat.
•
Thermostat settings
(only available in thermostats Blueface)
.
Use this parameter to define the thermostat as Master or
Zone.
*Note:
It cannot be configured as Master if there is already another Master thermostat (except for 4-pipe installations).
•
Use mode.
The thermostats can be set in Basic or Advanced mode. They are set in Advanced mode by default. These
are the parameters you can control in basic mode: On/off, set-point temperature, fan speed and operation mode (only
available for zone thermostats in installations configured as four-pipe).
If you need to reset the thermostat to Advanced mode, access the advanced configuration menu and then activate
the advanced use mode.
•
Control stages
(only available in installations with AZDI6OUTPUT8 modules).
This parameter is used to configure both
cooling and heating stages in a single zone or in all the zones. These are the features to be configured:
-
Air: It activates the heating/cooling air in the zone.
-
Radiant:
It activates radiant heating/cooling.
-
Combined: It activates both air and radiant heating/cooling in the zone selected and also allows the user to select
the desired heating stage: Air, Radiant or Combined. The zone will start using the heating air stage and once the
room temperature reaches a pre-established differential (check
), the zone will activate the radiant
stage.
-
Off: It deactivates the cooling/heating stage in the zone.
•
Offset.
Correction factor for the room temperature of the zones (range: from -2.5˚C to 2.5 ˚C in steps of 0.5 ˚C). It is in
0˚C by default.
•
Presence contact.
It determines the state of the module of a zone based on the occupancy. It only has effect on the
zone control module if it is associated to a thermostat (it does not operate in secondary zone modules). When this
contact is on, if the zone is empty for over 5 minutes, the Sleep 90 feature is activated (displaying an Occupancy
notification on the thermostat). It is off by default. In order to activate this feature, configure it as Normally open or
Normally closed.