High-Limit Thermostats

Introduction:

The Aqua-Hot is equipped with three resettable High-Limit 

Thermostats. These thermostats are in place to prevent the 

heater from operating beyond its safe operational threshold. 

These thermostats are resettable and easily replaceable. 

 

Begin troubleshooting the High-Limit Thermostats if the 

controller issues an overheat fault, or the electric and/or diesel 

burner fail to operate correctly.

Troubleshooting Guidelines:

The following conditions must be met before the High-Limit 

Thermostats can be diagnosed, and if necessary, repaired.
• 

The fluid expansion bottle is filled to at least the “COLD” 

mark.

•  Verify that all in-line fuses are functional.
•  Ensure that the unit is completely cool.
•  Ensure that DC electrical power is supplied to the Aqua-Hot.
•  Ensure that AC electrical power is supplied to the Aqua-

Hot’s electric element.

If any of the above conditions are not met, correct them before 

continuing with troubleshooting. Results of the troubleshooting 

procedure cannot be verified if the conditions listed above are 

not fulfilled.

Troubleshooting Procedure:

Locate the high-limit 

thermostat which is 

suspected of failure

Using a multi-meter, test 

for continuity across this 

thermostat

Is continuity present 

across this thermostat?

Yes

No

Depress the red button in 

the center of the high limit 

thermostat (Figure 40)

Re-test for continuity

Does the thermostat now  

have continuity?

Yes

No

This thermostat is 

functioning as intended.

This 

thermostat is 

functioning as 

intended.

Replace this 

thermostat

AC High 

Limit

Left High 

Limit

Right High 

Limit

Figure 39

Figure 40

Replacement Procedure:

If it has been determined that one, or multiple high-limit 

thermostats need to be replaced, they can be easily replaced 

by following the directions below.
1.  Disconnect all sources of AC and DC power from the Aqua-

Hot (if the AC high-limit thermostat is the issue, the AC 

access cover will need to be removed - see Figure 41).

2.  Disconnect the wires which connect to the non-functional 

high-limit thermostat.

3. 

Using a ⅝” (16mm) wrench, remove the thermostat from 

its location on the fluid tank. Reference Figure 42 for the 

DC high-limit thermostat removal and Figure 43 for the AC 

high-limit thermostat removal.

4.  Locate the new thermostat and secure it in place of the old 

thermostat

5.  Reconnect the disconnected wires as described by the 

table below. 

High Limit Thermostat

Wires

Left

J6-3 and BOT1

Right

BOT1 and J6-3-HL

AC

AOT1 and AOT2

6.  Test the Aqua-Hot for normal operation.

If issues persist, please contact Aqua-Hot Heating Systems for 

additional assistance.

NOTE: 

The AC access cover will need to be removed if the AC 

high-limit thermostat is the issue or needs to be tested. See 

the image below.

Figure 42

Figure 41

Figure 43

AC Cover Removal

AC High-Limit Thermostat Removal

DC High-Limit Thermostat Removal (Right)

Summary of Contents for Aqua-Hot 100 Series

Page 1: ...Service Manual 100Series AHE 125 DN1...

Page 2: ...ed by transfer from the heated antifreeze and distilled water solution The heated domestic water then flows through the tempering valve to be mixed with cool water from the fresh water tank to achieve...

Page 3: ...a Hot please contact our Technical Service Department at 574 AIR XCEL 574 247 9235 from 7 00am to 4 00pm MST Monday through Friday As with any appliance allow the Aqua Hot to completely shut down BEFO...

Page 4: ...cing disconnect all power supplies DO NOT operate the diesel burner and or electric heating element without antifreeze and distilled water heating solution present in the Aqua Hot s boiler tank Doing...

Page 5: ...2 Tempering Valve 3 Aqua Hot Controller 4 Antifreeze and Water Heating Solution Tank 5 AC Electric Element 6 AC Activation Relay 7 Plate to plate Heat Exchanger 8 Three Way Valve 9 Zone Air Bleed Val...

Page 6: ...LCD screen From here the end user will select their interior temperature set points activate or deactivate the diesel burner and the electric element Zone Control 1 Precise zone control display will d...

Page 7: ...utilized with the Aqua Hot 5in display Using the Aqua Hot with this new display will ensure that you can take advantage of all of the tools and features of this controller Features This new controller...

Page 8: ...dicates that heat is either not needed or not requested by the zone thermostat 71 This indicates the set point of the coach thermostats The example in Figure 18 is showing the coach thermostat is requ...

Page 9: ...ones have been directly wired to the Aqua Hot as described in the installation manual Heating sub systems can be activated independent of their control circuits and other control sensors as a means of...

Page 10: ...ate Ensure the controller is properly oriented reference Figure 32 10 Using the 4 nuts previously removed fasten the controller to the mounting plate 11 Insert the controller and mounting plate into t...

Page 11: ...to the INPUTS FROM AQUA HOT section HOME Aqua Hot Diagnostics DIAG Locate LLCO Does LLCO display TANK FULL Yes No This fluid level sensor is functioning as intended Replace the controller Troubleshoo...

Page 12: ...this thermostat Yes No Depress the red button in the center of the high limit thermostat Figure 40 Re test for continuity Does the thermostat now have continuity Yes No This thermostat is functioning...

Page 13: ...inue troubleshooting to the right Open a hot water faucet within the coach 1 1 2 2 Figure 47 Continue trouble shooting here Low Temperature Cutoff Thermostat Introduction The Low Temperature Cutoff Th...

Page 14: ...s of the Three Way Valve to ensure it is out of the way 6 On the top of the Three Way Valve move the two 2 constant tension clamps AWAY from the tee fitting so that they are as far from the barb as po...

Page 15: ...the Aqua Hot and slide the red and blue PEX through their ports in the front face of the Aqua Hot Use soapy water as necessary to lubricate the PEX going through the rubber grommets in the ports DO NO...

Page 16: ...Figure 60 If no functionality replace the AC electric relay Figure 59 If tank temperature is not 180 F check element for 11 2 13 amps Replace the Electric element This AC Electric system is operating...

Page 17: ...switch the electric heating element on and off in conjunction with the interior switch panel and ETS module even though the electric element is on a separate circuit Troubleshooting Procedure Trouble...

Page 18: ...ely the same Yes This ETS module is functioning as intended Disconnect the ETS module from its leads on the wire harness Navigate back to the INPUTS FROM AQUA HOT section of the LCD screen No Yes No D...

Page 19: ...Requirements Parts needed PLX 125 HA1 High Altitude Kit Potential other parts needed PLE 125 FL1 Kit 100 Series Fuel Line only if fuel lines are damaged PLX 125 003 Fuel Filter 100 Series only if fue...

Page 20: ...Pins Figure 79 1 2 Ground goes to Pin 1 Power goes to Pin 2 If you would rather use a plug instead of the wire and gator clips the mating part numbers needed for the connector are Housing 1 967644 1 T...

Page 21: ...uction A lack of interior heat or hot water when provided with adequate heat from either the electric element and or the diesel burner can be attributed to an overheat thermostat the Aqua Hot controll...

Page 22: ...rner Troubleshooting This section will cover any issues with the external diesel burner The diesel burner is the primary heat source to the 125DN The troubleshooting procedures listed below are arrang...

Page 23: ...or damage Check plumbing lines and circulation pump to make sure they are properly secured and free of any damage Check the fuel pump and circulation pump for any damage Run the burner for 20 minutes...

Page 24: ...System Schematics System Schematics Aqua Hot 125 DN1 Service Manual REV 220421 Aqua Hot 125 DN1 Service Manual REV 220421 p 47 p 46 ZONE THERMOSTATS ZONE HEAT EXCHANGERS...

Page 25: ...System Schematics System Schematics Aqua Hot 125 DN1 Service Manual REV 220421 Aqua Hot 125 DN1 Service Manual REV 220421 p 49 p 48 EXTERNAL DIESEL BURNER ELECTRIC ELEMENT...

Page 26: ...de Connectors ELE 014 711 Thermistor Tank Temperature Sensor ELE 102 201 Aqua Hot AC Harness ELE 102 211 Burner DC Harness ELE 400 900 Harness Buehler C20 Pump ELX THM 309 Thermistor 10K NTC Room Temp...

Page 27: ...00 Low Temperature Cutoff Thermostat w Spade Terminals ELX 2E7 102 125DN Element 1 NPSM 120 VAC 1500W Heating MSX 907 162 Refractometer EXE 103 0EX Heat Exchanger Cozy III PLX CTB 290 Clamp Hose Const...

Page 28: ...that is complete peer through the eyeglass of the refractometer to continue to the next step Adjust the Boundary Line Once the glycol solution has been properly applied adjust the calibration screw u...

Page 29: ...Heating Systems LLC 7501 Miller Drive Frederick CO 80504 Visit us online at www aquahot com Call us at 574 AIR XCEL 574 247 9235 2022 Aqua Hot Heating Systems LLC Printed in the USA Service Manual 10...

Reviews: