TROUBLESHOOTING
13-4
Service Manual – YBZ DCI 1-A.1 GB
13.1.4
Fault Code display from IDU
If the malfunction still exists 4min later after stop of unit due to compressor protection, error code will be
directly displayed though indoor display. In other situations, fault code can be displayed by pressing
LIGHT button 6 times within 4s.
Fault code can be displayed on 2*7 segments or by the LEDs blinking (OFF for 3s and then with certain
blinking as following)
LEDs blinking
Fault description
2* 7
segments
RUN
COOL
HEAT
Possible Reason
HP switch protection
E1 1
1. Refrigerant
was
superabundant
2. Poor heat exchange (including blockage
and bad radiating environment )
3. Too high ambient temperature
Indoor coil defrost Protection
E2
2
1. Poor air-return in indoor unit
2. Fan speed is abnormal
3. Evaporator is dirty.
Compressor over Heating
Protection
E4 4
1. EEV connection problem or damage
2. Refrigerant
leakage
3. Poor heat exchange
AC Over current protection
E5
5
1. Supply voltage is unstable
2. Supply voltage is too low and load is too
high
Communication malfunction
E6
6
1. Wiring
mistakes
2. IDU or ODU PCB problem
Mode conflict
E7
7
Mode conflict to other IDU
Indoor coil/Outdoor coil over
heating protection
E8 8
1. Too high ambient temperature
2. Poor heat exchange (including blockage
and bad radiating environment )
No feedback of indoor motor
H6
11
1. IFAN motor damaged
2. IFAN motor blocked
3. IDU PCB problem
Malfunction protection of jumper
cap
C5
15
Poor connection of the jumper on indoor PCB.
Zero-crossing protection (IDU)
U8
17
1. IFAN motor damaged
2. Zero-crossing circuit damaged on IDU
PCB
Mismatch of IDU and ODU
LP
19
RAT failure
F1
1
ICT failure
F2
2
OAT failure
F3
3
CTT failure
F5
5
1. Senor was broken or damaged
2. PCB temperature detection circuit has
problem
DC over voltage
PH
11
1. AC input voltage is too high.
2. Reactor has problem
3. ODU PCB has problem
OCT failure
F4
18
RLT failure
b5
19
RGT failure
b7
22
1. Senor was broken or damaged
2. PCB temperature detection circuit has
problem
Compressor overload protection
H3
3
1. EEV connection problem or damaged
2. Refrigerant
leakage
3. OLP
damaged
IPM protection
H5
5
1. Abnormal power input voltage.
2. Compressor
wiring
mistake.
3. Liquid and gas valve are not open.
4. EEV damaged or not proper working
5. Poor heat exchange.
6. Over charged system.
Summary of Contents for YBZ214
Page 16: ...OUTLINE DIMENSION 4 2 Service Manual YBZ DCI 1 A 1 GB 4 2 Indoor HZD018 HYD018...
Page 17: ...OUTLINE DIMENSION Service Manual YBZ DCI 1 A 1 GB 4 3 4 3 Outdoor YBZ214...
Page 18: ...OUTLINE DIMENSION 4 4 Service Manual YBZ DCI 1 A 1 GB 4 4 Outdoor YBZ318 YBZ430...
Page 35: ...WIRING DIAGRAM 9 2 Service Manual YBZ DCI 1 A 1 GB 9 3 YAZ214...
Page 36: ...WIRING DIAGRAM Service Manual YBZ DCI 1 A 1 GB 9 3 9 4 YAZ318...
Page 37: ...WIRING DIAGRAM 9 4 Service Manual YBZ DCI 1 A 1 GB 9 5 YAZ430...
Page 38: ...WIRING DIAGRAM Service Manual YBZ DCI 1 A 1 GB 9 5 9 6 Wiring connection between IDU and ODU...
Page 39: ...WIRING DIAGRAM Service Manual YBZ DCI 1 A 1 GB 10 1 10 REFRIGERATION DIAGRAMS...
Page 40: ...TUBING CONNECTIONS Service Manual YBZ DCI 1 A 1 GB 11 1 11 TUBING CONNECTIONS...
Page 76: ...EXPLODED VIEW SPARE PART LIST Service Manual YBZ DCI 1 A 1 GB 15 15 APPENDIX...