Indoor Fan Control
8 Indoor fan speeds are determined for each model. 4 speeds for COOL modes and 4 speeds for
HEAT mode.
Unit Model
Mode
Turbo(Super high)
High
Medium
Low
Cooling 1300
1100 900 700
09
Heating 1300
1140 980 820
Cooling 1350
1150 950 750
12
Heating 1350
1190 1020 850
Cooling 1350
1100 950 800
18
Heating 1400
1200 1050 900
In high/ medium/ low indoor fan user setting, unit will operate fan in selected speed.
In Auto Fan user setting, fan speed will be adjusted automatically according to the difference
between actual room temperature (RAT) and user set point temperature (SPT).
Indoor Fan speed
High
Medium
Low
Cooling
>=2 (0,2) <=0
RAT-SPT
Heating
<=1 (1,3) >=3
During Auto Fan operating, one speed should keep at least 210sec operating before switching to
other speeds.
In DRY mode, the automatic fan speed is forced to be low.
12.1.3.1 Turbo Speed
In COOL and HEAT mode (not available in AUTO, DRY, FAN mode), press the Turbo button, the
super high fan speed is selected on Remote control and the indoor fan rotates at super high speed.
12.1.4
Outdoor Fan Control
The outdoor fan motor is a 3 speed AC motor and controlled by the relays on outdoor controller.
OFAN speed will be changed according to OAT temperature.
12.1.5 EEV
Control
12.1.5.1 EEV
homing
When compressor stops or unit is power on, the following is performed immediately:
-
All EEV’s are closed 520 steps and then set this opening as 0 step
.
-
Then All EEVs are opened 480 steps and ready for system staring.
Summary of Contents for YBZ214
Page 16: ...OUTLINE DIMENSION 4 2 Service Manual YBZ DCI 1 A 1 GB 4 2 Indoor HZD018 HYD018...
Page 17: ...OUTLINE DIMENSION Service Manual YBZ DCI 1 A 1 GB 4 3 4 3 Outdoor YBZ214...
Page 18: ...OUTLINE DIMENSION 4 4 Service Manual YBZ DCI 1 A 1 GB 4 4 Outdoor YBZ318 YBZ430...
Page 35: ...WIRING DIAGRAM 9 2 Service Manual YBZ DCI 1 A 1 GB 9 3 YAZ214...
Page 36: ...WIRING DIAGRAM Service Manual YBZ DCI 1 A 1 GB 9 3 9 4 YAZ318...
Page 37: ...WIRING DIAGRAM 9 4 Service Manual YBZ DCI 1 A 1 GB 9 5 YAZ430...
Page 38: ...WIRING DIAGRAM Service Manual YBZ DCI 1 A 1 GB 9 5 9 6 Wiring connection between IDU and ODU...
Page 39: ...WIRING DIAGRAM Service Manual YBZ DCI 1 A 1 GB 10 1 10 REFRIGERATION DIAGRAMS...
Page 40: ...TUBING CONNECTIONS Service Manual YBZ DCI 1 A 1 GB 11 1 11 TUBING CONNECTIONS...
Page 76: ...EXPLODED VIEW SPARE PART LIST Service Manual YBZ DCI 1 A 1 GB 15 15 APPENDIX...